Troubleshooting
Diagnosis (service scans)
Fault index "Err" (Table E)
Posi-
Active
tion
code
Components and fault messages reported directly by EEV controller.
1
1
2
2
1
2
4
8
3
0
4
0
Messages
5
1
82
(cont.)
Explanation
Liquid gas temper-
ature sensor
faulty.
EEV stepper motor
faulty.
Low pressure sen-
sor faulty.
Suction gas tem-
perature sensor
faulty.
High pressure sen-
sor faulty.
Hot gas tempera-
ture sensor faulty.
N/A
Inadequate evapo-
ration pressure
(low pressure
fault).
System charac-
teristics
■ Compressor
remains in oper-
ation.
■ Energy state-
ment (see
page 91) will
not be calculated
correctly.
Compressor is
switched off.
Compressor is
switched off.
■ Compressor
remains in oper-
ation.
■ Energy state-
ment (see
page 91) will
not be calculated
correctly.
Compressor is
switched off.
Measures
Check sensor;
replace if required.
Replace EEV.
Check sensor;
replace if required.
As for "D3 Low
pressure" (see
page 62).