Viessmann VITOTRONIC 200 Service Instructions Manual page 159

Vitotronic 200 type wo1a heat pump control unit
Table of Contents

Advertisement

Main and extension PCB
Plug sXF
Terminals
Function
224.4
Control of instantaneous
heating water heater,
stage 2.
2.
r
224.5
:
Circulation pump for cylinder
heating for heat pump stage
2.
:
2.
Fan stage 2 (factory connec-
tion).
224.6
■ Cylinder primary pump
(DHW side)
■ 2-way shut-off valve
M
224.7
Circulation pump for DHW
reheating
or
Immersion heater control
(cont.)
Explanation
Connection values
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 4 (2) A
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4 (2) A
Connect cylinder primary pump and 2-
way shut-off valve in parallel.
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4 (2) A
Connection values
■ Output: 100 W
■ Voltage: 230 V~
■ Max. switching current: 4 (2) A