Installation

Connection of the Boiler Temperature Sensor

3
760
740
720
700
680
660
640
620
600
580
560
540
400
0
20
40
32
68
104
Boiler temperature in
50
60
80
100
120
141
176
212
248
°C / °F
Electrical connection
See page 42.
The sensor measures the boiler
water temperature of the boiler.
The boiler temperature sensor is
installed at the same time as the
boiler insulation.
Check the sensor
1. Disconnect plug § in the
terminal compartment.
2. Measure resistance of sensor at
terminals "1" and "2" of the plug
or "2" and "3" (if a second DHW
tank temperature sensor is
connected).
Boiler water
temperature
in °C / °F
40 / 104
50 / 122
60 / 140
3. Compare the value measured with
the current temperature. If the
value differs significantly, check
installation and, if necessary,
replace sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
during operation:
0 to + 130°C
32 to + 266°F
during storage and transport:
-20 to + 170°C
- 4 to + 158°F
Electrical connection
The sensors are ready to plug in.
Insert the boiler temperature sensor
in socket "3" of the boiler control.
140
284
Resistance
in Ω Ω Ω Ω
578
597
616