Troubleshooting
Repairs
(cont.)
Check the temperature limiter
92
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 75 °C:
&
Pull the leads from thermocouple
A.
&
Check the continuity of the thermo-
couple with a multimeter.
&
Remove the faulty thermocouple.
&
Install a new thermocouple.
&
After commissioning, press reset
button E on the control unit.