Viessmann Vitodens 200 Service Manual page 79

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Checking and acknowledging faults
Fault code
Const.
in the dis-
play
C6
C7
X
Cd
X
CE
X
CF
dA
db
Weat-
System
h.
character-
comp.
istics
X
Control
mode,
max. pump
speed
X
Control
mode,
max. pump
speed
X
Control
mode
X
Control
mode
X
Control
mode
X
Control
mode with-
out room
influence
X
Troubleshooting
(cont.)
Cause
Remedy
Communication
Check set-
fault - variable
tings of cod-
speed heating cir-
ing address
cuit pump, heating
E5; check the
circuit M2
heating cir-
cuit pump
DIP switch
settings.
Communication
Check setting
fault - variable
of coding
speed heating cir-
address E5;
cuit pump, heating
check the
circuit A1
heating cir-
cuit pump
DIP switch
settings.
Communication
Check con-
fault Vitocom 100
nections and
(KM BUS)
Vitocom 100
Communication
Check con-
fault - ext. exten-
nections and
sion
coding
address 2E
settings
Communications
Replace the
fault - LON commu-
LON commu-
nication module
nication mod-
ule
Room temperature
Check the
sensor heating cir-
room tem-
cuit A1 shorted out
perature sen-
sor for
heating cir-
cuit A1
Heating circuit M2
Check the
room temperature
room tem-
sensor shorted out
perature sen-
sor for
heating cir-
cuit M2
79