Viessmann Vitodens 200 Service Manual page 61

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
F2:8
*
2
Time limit for party
operation 8 hours or
external operating
mode changeover via
push button
F5:12
*
4
Run-on time of the
internal circulation
pump in heating mode
F6:0
*
4
In the "DHW only"
operating mode, the
internal circulation
pump is permanently
OFF
F7:10
*
4
In "Standby mode",
the internal circulation
pump will be started 10
times per day for
10 minutes respectively
*2
Only for weather-compensated control units
In heating program rw, the party mode ends automatically when changing over to
*3
operation with standard room temperature.
*4
Only for constant temperature control units.
Coding
change
Address:
value
F1:6
to
F1:15
F2:0
F2:1
to
*
3
F2:12
F5:0
F5:1
to
F5:20
F6:1
to
F6:24
F6:25
F7:0
F7:1
to
F7:24
Coding
Possible change
the address is manually
set to 0.
Constant flow tempera-
ture 20 °C
No time limit for party
mode
Time limit adjustable from
*
3
1 to 12 hours
No run-on time of the
internal circulation pump
Run-on time of the inter-
nal circulation pump
adjustable from 1 to
20 minutes
In the "DHW only" operat-
ing mode, the internal cir-
culation pump will be
started 1 to 24 times per
day for 10 minutes,
respectively
In the "DHW only" operat-
ing mode, the internal cir-
culation pump is
permanently ON
In "Standby mode", the
internal circulation pump
is permanently OFF
In "Standby mode", the
internal circulation pump
will be started 1 to 24
times per day for
61