Viessmann Vitodens 200 Service Manual page 15

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Further details regarding the individual steps
Supply (flow)
Supply (flow)
pressure for nat-
pressure for
ural gas
LPG
Below 17.4 mbar
Below 42.5 mbar
17.4 to 57.5 mbar
42.5 to
57.5 mbar
In excess of
In excess of
57.5 mbar
57.5 mbar
Initial start-up, inspection, maintenance
(cont.)
5. Start up boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 seconds, press E to
reset the burner.
6. Check the supply (flow) pressure; it
should be
&
20 mbar for natural gas,
&
and 50 mbar for LPG.
Note
Use suitable test equipment with a
resolution of at least 0.1 mbar to
measure the supply pressure.
Record the actual value in the ser-
vice report.
Take the action shown in the table.
Remedy
Do not start up. Notify your mains gas or
LPG supplier.
Start up boiler.
Install a separate gas governor down-
stream of the system and regulate the
pressure to 20 mbar for natural gas or
50 mbar for LPG. Notify your mains gas
or LPG supplier.
7. Shut down the boiler, close the gas
shut-off valve, remove the pressure
gauge, and close test nipple A
with the screw.
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200 wb2a

Table of Contents