Viessmann Vitodens 200 Service Manual page 83

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Checking and acknowledging faults
Fault code
Const.
in the dis-
play
FA
X
Fd
X
FE
X
Weat-
System
h.
character-
comp.
istics
X
Burner in
fault state
X
Burner
blocked
X
Burner
blocked
Troubleshooting
(cont.)
Cause
Remedy
Fan stop not
Check the
achieved
fan, check the
fan cables,
check the fan
control
Press E
Burner control unit
Check the
fault
ignition elec-
trodes and
leads. Check
whether a
strong inter-
ference
(EMC) field
exists near
the equip-
ment.
Press E
If the fault is
not removed,
replace the
control unit.
Strong interference
Remove EMC
(EMC) field nearby;
interference.
alternatively boiler
If the equip-
coding card or
ment will not
main PCB faulty.
restart, check
the boiler
coding card
and replace,
or replace the
control unit.
83

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200 wb2a