Viessmann Vitodens 200 Service Manual page 49

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
Domestic hot water
56:0
DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary func-
tion for DHW loading
59:0
DHW cylinder loading:
Starting point -2.5 K
Stopping point +2.5 K
5B:0
DHW cylinder directly
connected to the boiler
60:20
During DHW loading,
the boiler water tem-
perature is max. 20 K
higher than set DHW
temperature
62:2
Circulation pump with 2
minutes run-on time
63:0
*
1
Without auxiliary
function for DHW load-
ing
*1
Only for constant temperature control units.
Coding
Possible change
change
Address:
value
56:1
DHW temperature adjus-
table from 10 to above
60 °C (subject to boiler
coding card; only for gas
fired boilers)
Observe the max. per-
missible DHW tempera-
ture
58:1
Input of a set DHW value
to
2; adjustable from 1 to
58:95
95 °C (observe coding
address 56)
59:1
Starting point adjustable
to
from 1 to 10 K below the
59:10
set value
5B:1
DHW cylinder connected
downstream of the low
loss header
60:5
The difference between
to
the boiler water tempera-
60:25
ture and the set DHW
temperature is adjustable
from 10 to 50 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 minutes
62:15
63:1
Additional function: 1 x
daily
63:2
every 2 to every 14 days
to
63:14
63:15
2 x daily
Coding
49