Viessmann Vitodens 200 Service Manual page 56

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Parameter address
A5:...
7
to
15
Coding in
Function mode
the as
delivered
condition
Address:
value
Boiler circuit, mixer circuit
*
1
A6:36
Extended economy
circuit inactive
*1
Only for weather-compensated control units
56
With heating circuit pump logic function: Heating
circuit pump OFF, if
AT > RT
- 1 K
Set
AT > RT
- 9 K
Set
Coding
change
Address:
value
A6:5
to
A6:35
Possible change
Extended economy cir-
cuit active, i.e. the burner
and heating circuit pump
will be switched OFF, and
the mixer will be closed at
a variable value, which is
adjustable between 5 and
35 ºC plus 1 ºC. This
value is based on the
adjusted outside tem-
perature, comprising the
actual outside tempera-
ture and a time constant,
which takes the cooling
down of an average
building into considera-
tion.