Viessmann Vitodens 200 Service Manual page 26

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Initial start-up, inspection, maintenance
Further details regarding the individual steps
Checking the ionisation current
A Adaptor line (available as acces-
sory)
26
(cont.)
1. Pull the line off and connect test
equipment (adaptor line available
as accessory).
2. Set the upper rated output.
Constant temperature control unit:
Press K and d simultaneously
&
for a minimum of 2 seconds.
With a/b in the display, select
&
2.
Weather-compensated control unit:
Press K and d simultaneously
&
for a minimum of 2 seconds.
With a/b in the display, select
&
"Full load".
Note
The minimum ionisation current
should be at least 4 µA as soon as
the flame is established (approx.
2 - 3 seconds after opening the gas
combination valve).
3. If the ionisation current is < 4 µA
&
Check the electrode gap, see
page 22.
&
Check the control unit power sup-
ply.
4. After testing, press d.
5. Record the actual value in the ser-
vice report.