Viessmann Vitodens 200 Service Manual page 17

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Further details regarding the individual steps
Initial start-up, inspection, maintenance
(cont.)
1. Connect a flue gas analyser at flue
gas connector A on the flue outlet.
2. Open the gas shut-off valve, com-
mission the boiler and create a heat
demand.
3. Select the lower rated output.
Constant temperature control unit:
Press both keys 9 and d simul-
&
taneously until the display shows
1.
Weather-compensated control unit:
Press both keys 9 and d simul-
&
taneously until the display shows
"Relay test".
With a/b in the display, select
&
"Basic load".
4. Check the CO
content. Should the
2
actual value deviate by more than
1 % from the above range, imple-
ment steps from page 16 (possibly
replace the burner).
5. Enter actual values into the service
report.
6. Set the upper rated output.
Constant temperature control unit:
With a/b in the display, select
&
2.
Weather-compensated control unit:
With a/b in the display, select
&
"Full load".
17