Viessmann Vitodens 200 Service Manual page 51

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Code 2
(cont.)
Coding in
Function mode
the as
delivered
condition
Address:
value
77:1
*
1
LON user number
79:1
*
1
Control unit is fault
manager
7b:1
*
1
Send time to LON
7F:1
*
1
Detached house
80:1
With 5 seconds time
delay for fault message;
message will be issued,
if a fault persists for at
least 5 seconds
81:1
Automatic summer/win-
ter changeover
88:0
Temperature display in
°Celsius
8A:175
Do not adjust
*1
Only for weather-compensated control units
Coding
Possible change
change
Address:
value
77:2
LON user number, adjus-
to
table from 1 to 99:
77:99
1 - 4 = boiler
5 = cascade
10 - ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once
79:0
Control unit is not fault
manager
7b:0
Do not send time to LON
7F:0
Multi-occupancy house:
Separate adjustment for
holiday program and time
program for DHW load-
ing, as option
80:0
Without time delay
80:2
Time delay adjustable
to
from 10 s to 995; 1 step =
80:199
5 s
81:0
Manual summer/winter
changeover
81:2
The application of the
radio clock module will be
recognised automatically
81:3
Accept time via LON
88:1
Temperature display in
Fahrenheit
Coding
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitodens 200 wb2a

Table of Contents