Viessmann Vitodens 200 Service Manual page 80

8.8 to 26.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Fault code
Const.
in the dis-
play
dd
dE
E4
X
E5
X
E6
X
F0
X
80
Weat-
System
h.
character-
comp.
istics
X
X
X
Burner
blocked
X
Burner
blocked
X
Burner in
fault state
X
Burner
blocked
(cont.)
Cause
Remedy
Room temperature
Check the
sensor heating cir-
room tem-
cuit A1 lead break
perature sen-
sor for
heating cir-
cuit A1
Heating circuit M2
Check the
room temperature
room tem-
sensor lead break
perature sen-
sor - heating
circuit M2
Fault - supply vol-
Replace con-
tage
trol unit
Internal fault
Check the
ionisation
electrode and
leads. Check
flue gas sys-
tem for
soundness.
Press E
Flue gas/air supply
Check the
system blocked
flue gas/air
supply sys-
tem. Check
the air pres-
sure switch
and the inter-
connecting
cables.
Press E
Internal fault
Replace con-
trol unit