Customer Interface - GE Digital Energy SitePro 400 VAC CESeries 7 Operating Manual

Uninterruptible power supply
Table of Contents

Advertisement

9

CUSTOMER INTERFACE

9.1
CUSTOMER INTERFACE
J5
X1
X2
JP3
J4
J2
J3
Fig. 9.1-1 Customer interface
The connectors A-J2 and B-J3 can be used for additional Advanced SNMP Card or an additional Customer
Interface (installation only when the UPS is switched Off).
Output signals on voltage-free contacts
On terminals X1 or J2 connector, six of the following 27 signals
can be selected from the display, entering with the appropriate
password.
0- No Information
1- Buzzer
2- General Alarm
3- Load on Mains
4- Stop Operation
5- Load on Inverter
6- Mains Failure
7- DC Over Voltage
8- Low Battery
9- Overload
10- Overtemperature
11- Inverter-Mains not synchr.
12- Bypass Locked
13- Bypass Mains Failure
Modifications reserved
OPM_SPE_XXX_60K_60K_7GB_V010.doc
Serial port J3 - RS232 (sub D - female 9 pin)
Pin 2: TX (out)
J2 (sub D-female 25p) – Output signals on voltage free contacts
J2 / 1, 2, 3
J2 / 4, 5, 6
J2 / 7, 8, 9
J2 / 14, 15, 16
J2 / 17, 18, 19
J2 / 20, 21, 22
Signals on terminals X1 and on connector J2 are in parallel and therefore not
separated galvanically from each other.
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for "16 - Manual Bypass ON" and "26 - EPO".
X1 terminals – Output signals on voltage free contacts
X1 / 1, 2, 3
X1 / 4, 5, 6
X1 / 7, 8, 9
X1 / 12, 13, 14
X1 / 15, 16, 17
X1 / 18, 19, 20
X2 – Terminals for EPO (Emergency Power Off) connection
X2 / 1, 2 or J2 / 12, 25
Note: to enable this function, remove the Jumper JP3 on P4 – Customer Interface board.
X1 / 10, 21 or J2 / 10, 23
X1 / 11, 22 or J2 / 11, 24
NO = Normally Open
14- Rectifier Mains Failure
15- Battery Discharge
16- Manual Bypass ON
17- Rectifier ON
18- Inverter ON
19- Boost Charge
20- Battery Earth Fault
21- Battery Fault
22- Relay Input 1
23- Relay Input 2
24- Relay Output ON
25- Relay Output OFF
26- EPO
27- SEM Mode ON
Suitable for IMV protocol
Pin 3: RX (in)
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NO, C, NC
NC
Input contacts
NO
Programmable
NO
Programmable / Generator ON
C = Common
Programmable functions on input contacts
Some UPS functions can be activated with
parameters when an external Normally Open (NO)
contact is closed on:
X1/10, 21 - J2/10, 23 or X1/11, 22 - J2/11, 24
Selectable functions by changing parameters
(password required) are:
0 - No function
2 - Inverter OFF
4 - Status Relay
6 - External Bypass ON
7 - External Battery Fuses, or External K3
(See Alarm 4104 - "Battery Fuses")
Voltage free contacts:
Pin 5: GND
Mains Failure
Load on Inverter
Stop Operation
Load on Mains
General Alarm
Acoustic Alarm
Mains Failure
Load on Inverter
Stop Operation
Load on Mains
General Alarm
Acoustic Alarm
EPO (Emergency Power Off)
NC = Normally Closed
1 - Inverter ON
3 - Print All
5 - Generator ON
Max. DC / AC: 24V / 1.25A
IEC 60950 (SELV circuit)
Min. Signal Level: 5VDC/5mA
Pagina 76/90
Operatine Manual SitePro 60 kVA