5.2

CUSTOMER INTERFACE BOARD

22
11
21
10
20
9
19
8
X1
18
7
17
6
16
5
15
4
14
3
13
2
12
1
Fig. 5.2-1 Customer Interface Board
Output signals on voltage-free contacts
On terminals X1, 6 of the following 27 signals can be selected
from the display, entering with the appropriate password.
0- NO SIGNAL
1- BUZZER
2- GENERAL ALARM
3- LOAD ON UTILITY
4- STOP OPERATION
5- LOAD ON INVERTER
6- UTILITY FAILURE
7- DC OVERVOLTAGE
8- LOW BATTERY
9- OVERLOAD
10- OVERTEMPERATURE
11- INVERTER-BYPASS NOT SYNCHR.
12- BYPASS LOCKED
13- BYPASS UTILITY FAILURE
Modifications reserved
GE_UPS_ISG_TLE_SUL_40K_M15_1US_V010.docx
Critical Power
X1 terminal block – Output signals on voltage free contacts (see Section 9.2.1)
X1 / 1, 2, 3
NO, C, NC
X1 / 4, 5, 6
NO, C, NC
X1 / 7, 8, 9
NO, C, NC
X1 / 12, 13, 14
NO, C, NC
X1 / 15, 16, 17
NO, C, NC
X1 / 18, 19, 20
NO, C, NC
The programmable signals on X1 will be disabled with Q1 open, with the
exception of the signals for "16 - MANUAL BYPASS ON" and "26 –
EMERGENCY OFF (EPO)".
X1 terminal block – Input contacts (see Section 9.2.2)
X1 / 10, 21
X1 / 11, 22
NO = Normally Open
14- RECTIFIER UTILITY FAILURE
15- BATTERY DISCHARGE
16- MANUAL BYPASS ON
17- RECTIFIER ON
18- INVERTER ON
19- BOOST CHARGE
20- BATTERY EARTH FAULT
21- BATTERY FAULT
22- RELAY INPUT 1
23- RELAY INPUT 2
24- RELAY OUTPUT ON
25- RELAY OUTPUT OFF
26- EMERGENCY OFF (EPO)
27- SEM/IEMi MODE
UTILITY FAILURE
LOAD ON INVERTER
STOP OPERATION
LOAD ON UTILITY
GENERAL ALARM
BUZZER (acoustic alarm)
NO
Programmable
NO
Programmable / GENERATOR ON
C = Common
Programmable functions on input contacts
Some UPS functions can be activated with
parameters when an external Normally
Open (NO) contact is closed on:
X1/10, 21
Selectable
parameters (password required) are:
0 - NO FUNCTION
1 - INVERTER ON
2 - INVERTER OFF
3 – PRINT ALL
4 - STATUS RELAY
5 - GENERATOR ON
6 - EXTERNAL BYPASS
7 - BATTERY FUSES OR EXTERNAL K3
(See Alarm 4104 - Battery Fuses)
8 - SEM/IEMi CONTROL
Voltage free contacts:
Max. 24Vac / 1A or 60Vdc / 0,5A
IEC-UL-CSA 60950-1 (SELV circuit)
Min. Signal Level: 5Vdc / 5mA
Installation Guide TLE Scalable Series 40 - 150 UL S1
(def. Parameter RL=1)
(def. Parameter RL=3)
(def. Parameter RL=5)
(def. Parameter RL=2)
(def. Parameter RL=4)
(def. Parameter RL=6)