DESCRIPTION

3.1

BLOCK DIAGRAM AND MAIN ELEMENTS

The SitePro system can be divided into the following main elements:
Control system
SitePro is designed with microprocessor-controlled signal processing circuits.
The interface between the operator and the unit is provided by the monitoring system on the front
panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier
The standard rectifier consists of a 6-pulse SCR-bridge, which converts the 3-phase mains voltage into a
controlled and regulated DC-voltage.
This regulated DC-voltage is used to supply power to the inverter, and to provide charging power to the
battery.
Inverter
The inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and
frequency, which is completely independent and isolated from the AC-input voltage.
Automatic bypass
The automatic bypass consists of a static semiconductor-switch (SSM: Static Switch Module), used to
provide an uninterrupted transfer of the load from inverter to mains.
Back-feed Protection
All SitePro UPS's are equipped with an automatic system for the protection against voltage back feeding
towards Utility, through the bypass (Applied Standard IEC 62040-1).
This protection works automatically by opening contactor K6 (in series with the thyristors of the static
switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the maintenance bypass Q2.
Manual bypass
The manual bypass consists of a pair of manual switches Q1 and Q2, which removes the UPS from the
load for maintenance, while still supplying the load with power directly from the mains.
Battery
The battery supplies the DC power to the inverter when the mains is out of accepted tolerances.