GE Digital Energy SitePro 400 VAC CESeries 7 Operating Manual page 33

Uninterruptible power supply
Table of Contents

Advertisement

JP2
JP1
JB-1
Terminal units
On the parallel bus PCB P34 - IM0048, of the first and last units (terminal) of the parallel system the
Jumpers JP1, JP2, JP3 and JP4 MUST BE INSERTED.
JP2
JP1
JB (2)
JB (1)
Intermediate units
On the parallel bus PCB P34 - IM0048 of the intermediate units of the parallel system the Jumpers
JP1, JP2, JP3 e JP4 MUST BE REMOVED.
NOTE !
In a parallel system composed of 2 or more units, only the first and last units (having 1
input JA and JB free) have the Jumper JP1, JP2, JP3 and JP4 inserted on parallel bus
PCB "P34 – Bus Interface" (see Fig. 4.9.2-2 and Fig. 4.9.2-3).
Modifications reserved
OPM_SPE_XXX_60K_60K_7GB_V010.doc
JP3
JP4
JA-1
Fig. 4.9.2-2 Bus connection on terminal units
JP3
JP4
JA (2)
JA (1)
Fig. 4.9.2-3 Bus connection on intermediate units
P11
J52
J62
B
A
P13
P3
P11
J62
J52
B A
P13
P3
Pagina 33/90
Operatine Manual SitePro 60 kVA