10.5 CONNECTION FOR OPTIONS

WARNING !
The installation and cabling of the options must be performed by QUALIFIED
SERVICE PERSONNEL only.
MAKE SURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.
Refer to the "Safety prescriptions - Installation" described on Section 1.

10.5.1 Auxiliary Power Supply (APS) 24 VDC

PA = Auxiliary Power Supply 24 VDC
PA
Connection
Cable PA+ (black)
Cable PA- (grey)
Cable PA-L (black)
Cable PA-N (grey)
Cable PA-PE (yellow-green)
Modifications reserved
OPM_SPE_XXX_60K_60K_7GB_V010.doc
PA
M4x10
Fig. 10.5.1-1 Auxiliary Power Supply 24 VDC
From
PA - APS: PA+
PA - APS: PA-
PA - APS: L
PA - APS: N
PA - APS: PE
NOTE !
Clamp the cables with the cable-ties.
XB = Terminals for connection
_
XB
+
N
L
To
Terminal: XB1 (+)
Terminal: XB2 (-)
Terminal: F50 (L)
Terminal: XB3 (N)
UPS frame: PE (see Fig. 10.5.1-1)
Pagina 84/90
Operatine Manual SitePro 60 kVA