7.7

EVENTS (ALARMS AND MESSAGES)

Each of the following listed events can be displayed on the LCD screen or on PC where the "PowerJump
Manager" or "PowerJump DataShield" is installed.
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signalled with the LED alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the buzzer).
When in the alarms mode, the LCD screen displays a time ordered sequence of screens corresponding
to the last 256 alarms and messages, each screen indicating:
metering
01.01.2005
NR=255 Status=4A61
alarms
4115: LOW
BATTERY VOLTAGE
parameters

7.7.1 Alarms list

Code
Alarms
SETUP VALUES
4000
LOST
UPS
4004
FAILURE
BATTERY
4104
FUSES
RECTIFIER
4106
TRANSFORMER
OVERTEMPERATURE
RECTIFIER MAINS
4110
OUT OF TOLERANCE
LOW BATTERY
4115
VOLTAGE
HIGH BATTERY
4116
VOLTAGE
BATTERY
4117
EARTH FAULT
4118
BATTERY FAULT
TURN ON RECT.
4130
OR SHUTDOWN UPS
Modifications reserved
OPM_SPE_XXX_60K_60K_7GB_V010.doc
+
12:45:07
ok
Parameters are lost and have been replaced with default values.
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
This function, when enabled on input programmable relays
(password required), warns the user about the external battery
fuses failure or MCB opening, signalled by NO free contact.
The temperature sensor inside the input transformer winding
indicates overtemperature. Only the alarm is given.
The rectifier, when in an Off state, cannot start as long as this
condition persists.
Rectifier input mains is out of tolerance (voltage, frequency or
phase).
The battery has been discharged and reached "stop operation"
time-out (default 3 minutes), and the inverter will be shut down.
It will restart automatically only when the battery has
recharged enough for a minimum runtime.
Dangerous high UDC-Voltage.
Causes inverter shutdown.
Inverter restarts automatically after battery returns to normal
floating voltage.
A leakage current to earth has been detected on the DC circuit.
During battery test the voltage falls under the critical level
(depending setting parameters).
Battery test is stopped.
Rectifier and inverter are OFF.
The DC power supply is discharging the battery slowly.
Rectifier must be restarted or battery must be disconnected in
order to avoid damage.
1-
The date and time when the event occurred.
2-
The number of the event (255 = the most recent).
The standard code and the status word.
3-
Code with an explicit text description of the events.
Meaning
Pagina 57/90
Operatine Manual SitePro 60 kVA