Customer Interface - GE Digital Energy SG Series Installation Manual

Uninterruptible power supply 10, 20, 30 and 40 kva
Hide thumbs Also See for Digital Energy SG Series:
Table of Contents

Advertisement

g
4.1

CUSTOMER INTERFACE

J5
X1
JP3
J4
J2
J3
Fig. 4.1-1 Customer interface
The connectors J4 and J5 can be used for additional SNMP Card , Environmental Card (not available yet)
or an additional Customer Interface (installation only when the UPS is switched Off).
XA : terminals for 24VDC Auxiliary Power Supply connection.
Programmable user relays
On terminals X1 or J2 connector, six of the following 26
signals can be selected from the display, entering with the
appropriate password .
0- No Information
1- Buzzer
2- General Alarm
3- Load on Utility
4- Stop Operation
5- Load on Inverter
6- Utility Failure
7- DC Over Voltage
8- Low Battery
9- Overload
10- Over Temperature
11- Inverter-Utility not syncr.
12- Bypass Locked
13- Bypass Utility Failure
OPM_SGS_ISG_10K_40K_0US_V010.doc
4 CUSTOMER INTERFACE
Serial port J3 - RS 232 (sub D - female 9 pin)
Pin 2 : TX (out)
XA
J2 (subD-female 25p) – Output signals on voltage free contacts
J2 / 1, 2, 3
J2/4, 5, 6
1
J2/7, 8, 9
J2/14, 15, 16
2
J2/17, 18, 19
J2/20, 21, 22
3
Signals on terminals X1 and on connector J2 are in parallel
4
and therefore not separated galvanically from each other.
The programmable signals on X1 and J2 will be disabled with Q1
open, with the exception of the signals for "16 - Manual Bypass ON"
and "26 - EPO".
XB
X2 / 1, 2 or J2 / 12, 25
Note: to enable this function, remove cable short-circuiting XB / 2 – 3
and the Jumper JP3 on P4 – Customer Interface.
1
X1 – Output signals on voltage free contacts - terminals
2
X1/1, 2, 3
3
X1/4, 5, 6
X1/7, 8, 9
4
X1/12, 13, 14
X1/15, 16, 17
X1/18, 19, 20
X1/10, 21 or J2/10, 23
X1/11, 22 or J2/11, 24
NO = normally open
14- Rectifier Utility Failure
15- Battery Discharge
16- Manual Bypass ON
17- Rectifier ON
18- Inverter ON
19- Boost Charge
20- Battery Earth Fault
21- Battery Fault
22- Relay Input 1
23- Relay Input 2
24- Relay Output ON
25- Relay Output OFF
26- EPO (Emergency
Power Off)
41/45
Suitable for JUMP protocol
Pin 3 : RX (in)
-
NO, C, NC
- Utility Failure
-
NO, C, NC
- Load on Inverter
-
NO, C, NC
- Stop Operation
-
NO, C, NC
- Load on Utility
-
NO, C, NC
- General Alarm
-
NO, C, NC
- Acoustic Alarm
XB - Terminals for EPO connection
NC
-
NO, C, NC
- Utility Failure
-
NO, C, NC
- Load on Inverter
-
NO, C, NC
- Stop Operation
-
NO, C, NC
- Load on Utility
-
NO, C, NC
- General Alarm
-
NO, C, NC
- Acoustic Alarm
Input contacts
Programmable (default = RL1)
Programmable / Generator ON (NO) (def. = RL2)
C = common
XB : terminals for EPO connection.
Programmable functions on contacts (X1 - J2)
Some UPS functions can be activated with
parameters when an external Normally Open
contact is closed on:
X1-10, 21 / J2-10, 23
Selectable functions by changing parameters
(password required) are:
0 - No function
2 - Inverter OFF
4 - Status Relay
6 - External Bypass ON
7 - External Battery Fuses, or External K3.
See Alarm 4104 - "Battery Fuses".
Voltage free contacts: Max. DC / AC: 24V / 1.25A
IEC 950 (SELV circuit)
Min. Signal Level: 5VDC/50mA
Installation Guide SG Series 10, 20, 30 & 40 kVA
GE
Pin 5 : GND
(def. Param. RL=1)
(def. Param. RL=3)
(def. Param. RL=5)
(def. Param. RL=2)
(def. Param. RL=4)
(def. Param. RL=6)
EPO (Emergency Power Off)
(def. Param. RL=1)
(def. Param. RL=3)
(def. Param. RL=5)
(def. Param. RL=2)
(def. Param. RL=4)
(def. Param. RL=6)
NC = normally closed
or X1-11, 22 / J2- 11, 24
1 - Inverter ON
3 - Print All
5 - Generator ON