GE Digital Energy SitePro 400 VAC CESeries 7 Operating Manual page 38

Uninterruptible power supply
Table of Contents

Advertisement

alarm
service check
Fig. 6.2-1 LEDs on synoptic diagram
Fig. 6.2-2 LCD screen
Modifications reserved
OPM_SPE_XXX_60K_60K_7GB_V010.doc
General alarm condition
It blinks when one or more alarm is activated. The internal buzzer is ON.
The LED remains lighted (with alarm condition still present) and the buzzer
stops as the key "mute" has been pressed.
LED ON indicates that a regular maintenance service is needed.
May be reset by a service technician only.
See Section 11 – Maintenance.
The LED is ON also when the output switch Q1 is open, indicating that the
Inverter is in service mode, not supplying the load.
a)
LED ON indicates that the Battery reserve lasts for only 3 more minutes
(selectable).
b)
LED ON in case of overtemperature or overload >125% together with
missing Mains.
After the timeout the Inverter will shut down.
All LEDs ON indicate that the Battery is fully charged
LED a
Yellow:
• Fixed:
• Blinking: indicating Battery backup
LED b, c, d
Green:
• Each one indicating 25 % of Battery backup.
LEDs ON indicate the Load status of the UPS
LED d
red
LED c
yellow
LED b
green
LED a
green
indicating last 25 % of Battery backup.
(≥100 % load)
(100% load)
(66% load)
(33% load)
LEDs on synoptic diagram
LED 1
= Input Mains Rectifier (green)
LED 2
= Input Mains Bypass (green)
LED 3
= Rectifier ON (green)
LED 4a
= Discharging (yellow)
LED 4b
= Charging (green)
LED 5
= Inverter ON (green)
LED 6
= Load on Inverter (green)
LED 7
= Load on Mains (green)
LED 8
= Output Load Voltage (green)
LED 9
= Manual Bypass (Q2) ON (yellow)
User LCD Interface
Consist of an LCD screen, 4 lines with 20
characters each and six keys. It offers:
UPS
operating,
information.
History of events (alarms and messages).
Functionality can be programmed to meet
customer needs by changing parameters.
5%.
AC
and
DC
metering
Pagina 38/90
Operatine Manual SitePro 60 kVA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitepro 60 kva series 7

Table of Contents