7.2

EVENT SCREENS (Alarm)

Each of the following listed alarms or messages can be displayed on the LCD screen or
transmitted to a PC through the serial port RS232 or the SNMP card (optional).
Entering the Alarm mode, the LCD screen displays a sequence of screens corresponding to the
last 256 alarms & events, each screen indicating:
15.01.2003
12:15:45
N=255 C=4580
S=A588
7.2.1

Alarms list

Are defined alarms:
Code
Alarm
SETUP VALUES
4000
LOST
REGULATION BOARD
4001
FAILURE
UPS
4004
FAILURE
RECTIFIER FUSES
4100
FAILURE
K4 CLOSING
4102
FAILURE
K4 OPENING
4103
FAILURE
RECTIFIER MAINS
4110
OUT OF TOLERANCE
LOW BATTERY
4115
VOLTAGE
HIGH BATTERY
4116
VOLTAGE
OPM_LPS_33E_10K_30K_4CN_V010.doc
1. The exact date and time when the event occurred.
2. The event number (255 being the most recent), the
standard code and status code.
all the events which activate the LED Warning (yellow) and the buzzer in
order to alert the user about an abnormal situation.
Parameters are lost and have been replaced with default
values.
Voltage supply +/-15 VDC has been detected out of
tollerance on the P2 - Mainboard or the programmable
circuits are defective.
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
The trip indicator mounted on rectifier input fuses indicates a
blown fuse.
The rectifier is turned Off (K4 open) and the load will be
supplied by the battery.
K4 not closed despite a closing command being done.
The rectifier is switched OFF.
K4 not open despite an opening command being done.
The rectifier is switched OFF.
Rectifier input mains has been detected out of tolerance
(voltage, frequency or phase).
The battery has been discharged and reached "stop
operation" time-out (default 3 minutes), the inverter will be
shut down.
It restarts automatically only when the battery has recovered
energy to ensure min. a "stop operation" time to the actual
load.
Dangerous high UDC-Voltage.
Causes Inverter shutdown. inverter restarts automatically
after return to normal floating voltage.
Meaning
Operating Manual LP 33 / 10-20-30 kVA