6.3.1 Events (alarms and messages)

Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software "GE Data Protection" installed or with the monitoring system "GE Power Diagnostic".
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED Alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED Alarm and the acoustical alarm).

6.3.2 Alarms list

Code
Alarm
4000
SETUP VALUES LOST
4001
REGULATION BOARD FAILURE
4100
RECTIFIER FUSES FAILURE
4102
K4 CLOSING FAILURE
4103
K4 OPENING FAILURE
RECTIFIER UTILITY OUT
4110
OF TOLERANCE
4115
LOW BATTERY VOLTAGE
4116
HIGH BATTERY VOLTAGE
4118
BATTERY FAULT
TURN ON RECT.
4130
OR SHUTDOWN UPS
4140
RECTIFIER CONTROL FAILURE
Modifications reserved
OPM_LPS_3UO_80K_M10_1US_V010.doc
Parameters are lost and have been replaced with default
values.
Voltage supply +/-15 Vdc has been detected out of
tolerance on the P2 - Mainboard or the programmable
circuits are defective.
The trip indicator mounted on rectifier input fuses indicates
a blown fuse.
The rectifier is turned OFF (K4 open) and the load will be
supplied by the battery.
K4 not closed despite a closing command being done.
The rectifier is switched OFF.
K4 not open despite an opening command being done.
The rectifier is switched OFF.
Rectifier input utility has been detected out of tolerance
(voltage, frequency or phase).
The battery has been discharged and reached "stop
operation" time-out (default 3 minutes), the inverter will be
shut down.
It restarts automatically only when the battery has
recovered energy to ensure min. a "stop operation" time to
the actual load.
Dangerous high DC-Voltage.
Causes Inverter shutdown.
Inverter restarts automatically after return to normal
floating voltage.
During battery test the DC voltage falls under the critical
level.
If the boost voltage has not been reached within 24 hours,
then the charge voltage returns to floating voltage.
Battery test is stopped.
Rectifier and inverter are OFF.
The DC power supply is discharging the battery slowly.
Rectifier must be restarted or battery must be disconnected
in order to avoid damages.
Rectifier voltage hasn't reached the set value.
Probably fault on regulation loop.
The DC capacitors are not equally charged (more of 50 Vdc
of difference).
The rectifier is switched OFF.
Meaning
User Manual LP33 Series 80 & 100 UL S1
Page 29/66