6.3.1 Events (alarms and messages)

Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software "GE Data Protection" installed or with the monitoring system "GE iUPSGuard".
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED ALARM and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED ALARM and the acoustical alarm).

6.3.2 Alarms list

Code
4000
SETUP VALUES LOST
4001
REGULATION BOARD FAILURE
4004
UPS FAILURE ON PARALLEL SYSTEM
4006
BUS JA CRC FAILURE
4007
BUS JB CRC FAILURE
4008
BUS JA FAILURE
4009
BUS JB FAILURE
4010
CONNECTIVITY BUS FAILURE
4011
EARTH LEAKAGE CURRENT
4012
LOAD GROUND FAULT
4013
CAN BUS FAILURE
4100
RECTIFIER FUSES FAILURE
4102
K4 CLOSING FAILURE
4103
K4 OPENING FAILURE
Modifications reserved
GE_UPS_USM_TLE_SUL_M62_1M0_2US_V010.docx
Critical Power
Alarm
Description
Parameters are lost and have been replaced with
default values.
Please call nearest Service Center for intervention.
A blocked DSP on the Control board causes this
alarm, and consequently the shut-down of Rectifier
and Inverter and the opening of K3.
The master unit detected the slave unit missing on
the communication bus even though switch Q1 is
still closed.
The parallel communication bus system is subject to
high errors rate on channel JA.
The parallel communication bus system is subject to
high errors rate on channel JB.
There is an interruption in the channel JA of the
parallel communication bus system.
There is an interruption in the channel JB of the
parallel communication bus system.
The connectivity communication bus is faulty or
interrupted.
The unit has detected an earth leakage current
above a configured threshold (typically 5% of the
maximum rated input current).
Applicable to 3-wire (3ph+PE) distribution only.
The unit has detected load ground current above a
configured threshold.
Applicable to 3-wire (3ph+PE) distribution only.
The Control Panel communication bus is faulty or
interrupted.
The u-switch mounted on the Rectifier input fuses
indicates a blown fuse, and consequently it is shut
down.
Clearance of this condition allows you to restart the
Rectifier.
K4 not closed despite a closing command being
issued. Signaled by auxiliary contact.
Rectifier cannot start.
K4 not open despite an opening command being
issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier bridge.