ADEMCO Vista-10SE Installation And Setup Manual page 99

Hide thumbs Also See for Vista-10SE:
Table of Contents

Advertisement

BATTERY FUSE
(e.g. ADEMCO No. 90-12)
24 HR BATTERY STANDBY REQUIRED
FOR REPLACEMENT
FOR FIRE INSTALLATIONS. USE 12V,
USE SAME VALUE
17.2AH BATTERY FOR 500 mA AUX
POWER. SEE INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
BURGLARY STANDBY USE AT LEAST 4
HOURS.
BLACK
BATTERY
+
RED
12V, 4AH
CHARGING
+
CONNECTOR
VOLTAGE
TABS
13.8VDC
RED
SEALED LEAD ACID TYPE
JUMPER
BATTERY. NORMALLY
CUT FOR BELL SUPERVISION.
NEED NOT BE
REPLACED FOR AT
ALSO CONNECT A 1000 OHM
LEAST 3 YRS.
EOLR ACROSS SOUNDER
TO DETERMINE
1
2
3
TOTAL STANDBY
LOAD ON BATTERY,
ADD 100mA TO
TOTAL OF AUX.
POWER OUTPUT
AND REMOTE
KEYPAD
CURRENTS.
USE UL LISTED
LIMITED ENERGY
CABLE FOR
CONNECTIONS
TO 110VAC
UNSWITCHED
OUTLET (24HR)
PLUG-IN
TRANSFORMER
16.5VAC, 25VA
(e.g. ADEMCO 1321.
FOR
USE 1321CN
COMPLETE
in CANDA)
INFORMATION,
SEE
+
ALARM OUTPUT
INSTRUCTIONS
10.5-13.8VDC, 2A MAX.
N7227V5
(600mA MAX. FOR UL USAGE,
INCLUDING AUX. POWER)
STEADY FOR BURGLARY/PANIC, TEMPORAL
SOUNDING FOR FIRE (e.g. USE ADEMCO 740
SOUNDER, 702 OR 719 SIREN, OR 12V BELL)
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE
ALARM HEADQUARTERS OR A CENTRAL STATION SHALL
BE PERMITTED ONLY WITH THE PERMISSION OF THE
LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE
EMERGENCY NUMBER.
THESE OPTIONAL ITEMS
MAY ALSO BE USED
SEE THEIR INSTRUCTIONS
ADEMCO 5800TM
TRANSMITTER MODULE
(20mA)
3A
(for 5827BD Wireless
Bi-directional Keypad)
AND/OR
ADEMCO 4285/4286
VIP MODULE 160mA/300mA
AND/OR
ADEMCO ECP COMPATIBLE
LONG RANGE RADIO
BLK
RED
GRN
YEL
4
5
6
7
8
9
+
AUX. POWER
OUTPUT
10.5-13.8VDC
500mA MAX.
INTERRUPTS
FOR FIRE
ALARM RESET.
ALL CIRCUITS
ARE POWER
LIMITED.
NOTE:
KEYPAD
CURRENT
MUST BE
INCLUDED
IN AUX.
1000
CURRENT
OHMS
DRAIN
EOLR
REMOTE
CALCULA-
KEYPAD(S)
TIONS
• MAXIMUM LOOP RESISTANCE (EACH ZONE) 300 OHMS (PLUS EOLR)
• RESPONSE, ZONES 1-6: 300-500MSEC
REMOTE KEYPADS
• ZONE 3 CAN BE PROGRAMMED FOR N.C. SENSOR
FAST RESPONSE TO AN OPEN: 10MSEC MAX
SYSTEM MUST BE
• ZONE 5 CAN BE PROGRAMMED FOR USE AS A FIRE ZONE.
PROGRAMMED WITH A
6139 KEYPAD. IT NEED
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
NOT REMAIN IN SYSTEM
OPERATION IS SUBJECT TO THE FOLLOWING TWO
AFTER PROGRAMMING.
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
THE SYSTEM CAN USE:
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
6127 (20mA), 6128 (30mA),
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
6137 (85mA), 6138 (100mA),
THAT MAY CAUSE UNDESIRED OPERATION.
OR 6139 (100mA).
MULTIPLE KEYPADS MAY BE
USED, BUT USE MAX. OF
220 FT. OF #22 WIRE, OR
550 FT. OF #18 WIRE.
WARNING:
TO BE REMOVED. WEEKLY TESTING IS REQUIRED TO
ENSURE PROPER OPERATION OF THIS SYSTEM.
FOR UP TO 16 RF EXPANSION ZONES
ADEMCO 5881* Type
AUX PWR
RF RECEIVER
OUTPUT
WIRELESS ZONES
TERMINALS
5881L: UP TO 8
5881M/5881H/5881EH: UP TO 16
* 5882 Type in CANADA
SET UNIT'S DIP SWITCH
FOR DEVICE ADDRESS OF "0"
(See receiver's instructions)
OPTIONAL
ADEMCO No. 4204
RELAY MODULE (180mA MAX)
(4 OUTPUT RELAYS)
SET UNIT'S DIP SWITCH
FOR DEVICE ADDRESS OF "1"
(See unit's instructions)
10
11
12
13
14
1000
1000
1000
1000
OHMS
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
EOLR
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
OWNER'S INSTRUCTION NOTICE NOT
+
5
_
_
BLK
4
+
_
VIOLET
1000
OHMS
EOLR
HEAT
DETECTOR
15
16
17
18
19
20
TIP
RING
TIP
RING
(BROWN)
(GRAY)
(GREEN)
(RED)
HANDSET
INCOMING
PHONE
LINE
TELEPHONE WIRING
(VIA RJ31X* JACK DIRECT
CONNECT CORD)
*in CANADA, CA38A JACK
DOC LOAD NO.: 3
WARNING:
TO PREVENT RISK OF SHOCK, DISCONNECT
TELEPHONE LINE AT TELCO JACK BEFORE
1000
SERVICING THIS UNIT.
OHMS
EOLR
THIS EQUIPMENT SHOULD BE INSTALLED
IN ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARD 72,
CHAPTER 2 (NATIONAL FIRE PROTECTION
ASSOC., BATTERYMARCH PARK, QUINCY,
MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION, OPERATION, TESTING,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
RED
+
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B
LOCATED AT
LOWER RIGHT
OF CIRCUIT
BOARD
21
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
V10SE-032-V0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents