Section 11. Final Power-Up; Earth Ground Connections; Wiring The Ac Transformer - ADEMCO Vista-10SE Installation And Setup Manual

Hide thumbs Also See for Vista-10SE:
Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section

Earth Ground Connections

Wiring the AC Transformer

AC Power-Up
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Earth Ground Connections
The designated earth ground terminal (21) must be terminated in a good earth ground for
the lightning transient protective devices in this product to be effective.
The following are examples of good earth grounds available at most installations:
Metal Cold Water Pipe:
Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which
the ground lead is electrically connected and secured.
AC Power Outlet Ground:
Available from 3-prong, 120VAC, power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL-Listed
Ideal Model 61–035, or equivalent, available at most electrical supply stores.
Wiring the AC Transformer
1321 Transformer
Wire the 1321 Transformer to terminals 1 and 2 on the control board. See wiring table below
for wire gauge to use.
• Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire.
• Do not plug the transformer into the AC outlet until you are instructed to do so later in the
manual.
WIRING TABLE
Distance of Transformer
From the Control Panel
Up to 50 feet
50 – 100 feet
100 – 250 feet
WWW.DIYALARMFORUM.COM
S E C T I O N
Final Power-Up
Calculating the Battery Size Needed
Connecting the Backup Battery
Battery Tests
Wire Gauge
to Use
# 20
# 18
# 16
1 1
11–1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents