Accumulated Operating Time (N087, N088) - Omron SYSDRIVE 3G3MV User Manual

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Advanced Operation
·Values will be set in 0.01-Hz increments if the frequency is less than 100 Hz and 0.1-Hz
increments if the frequency is 100 Hz or over.
·These values must satisfy the following condition.
n083
n084
·The value in n086 must be set for the jump width.
·This function is disabled with n086 set to 0.0.
·The operation of the Inverter within the dead bands is prohibited. While the Inverter is
in acceleration or deceleration control, however, the Inverter does not jump the bands
but changes the frequency smoothly.
Frequency Jump Function
Output
frequency

Accumulated Operating Time (n087, n088)

6-10-7
The accumulated operating time function is provided for 5.5- and 7.5-kW Inverters
·
only.
This function calculates and stores in memory the Inverter's accumulated operating
·
time. The accumulated operating time that is saved can be checked (unit: 10h) by the
"accumulated operating time" (U--13) of the multi-function monitor (MNTR indicator).
Use this function in determining the maintenance schedule.
·
Accumulated Operating
n087
Time
Setting
0, 1
range
n085
Register 0157
Hex
Unit of
1
setting
Chapter 6
Reference
frequency
Changes during
No
operation
Default setting
0
6-45