Advanced Operation
·The stored output frequency will be cleared from the memory if n100 is set to 0. The
retained frequency is initialized if n001 for parameter initialization is set to 8 or 9.
Note While this function is used, frequency references can only be used in remote
mode with the UP/DOWN command or inching frequency command. All multi-
step speed references are disabled.
n100
UP/DOWN Frequency
Selection
Setting
0, 1
range
Set Values
Value
0
The frequency on hold is not retained.
1
The frequency on hold for 5 s or more is retained.
Operation of UP/DOWN Function
RUN command
(Forward rotation)
UP command
(S5)
DOWN command
(S6)
Output frequency
Upper limit
Lower limit
Status
Frequency
detection
Note
Status U: UP (acceleration)
D: DOWN (deceleration)
H: Hold
U1: Frequency acceleration restricted by upper limit.
D1: Frequency deceleration restricted by lower limit.
Register 0164
Hex
Unit of
1
setting
Description
Chapter 6
Changes during
No
operation
Default setting
0
Time
Time
Time
Time
Time
6-49