Advanced Operation
Number of Fault Retries
n082
Setting
0 to 10
range
Set Values
·Set the number of fault retries required.
·The count of fault retries will be cleared in any of the following cases.
The Inverter is normal for 10 minutes continuously after the latest fault retry was
made.
Power supply to the Inverter is interrupted.
A fault reset is input.

6-10-6 Frequency Jump Function (n083 to n086)

·The frequency jump function prevents the Inverter from generating frequencies that
make the mechanical system resonate.
·The frequency jump function can be used effectively to set three dead bands of a fre-
quency reference.
n083
Jump Frequency 1
Setting
0.00 to 400.0 (Hz)
range
n084
Jump Frequency 2
Setting
0.00 to 400.0 (Hz)
range
Jump Frequency 3
n085
Setting
0.00 to 400.0 (Hz)
range
Jump Width
n086
Setting
0.00 to 25.50 (Hz)
range
Set Values
·Set n083 through n085 for jump frequencies 1 through 3 to the central values of jump-
ing frequencies.
6-44
Register 0152
Hex
Unit of
1
setting
Register 0153
Hex
Unit of
0.01 Hz
setting
Register 0154
Hex
Unit of
0.01 Hz
setting
Register 0155
Hex
Unit of
0.01 Hz
setting
Register 0156
Hex
Unit of
0.01 Hz
setting
Chapter 6
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0.00
Changes during
No
operation
Default setting
0.00
Changes during
No
operation
Default setting
0.00
Changes during
No
operation
Default setting
0.00