Advanced Operation
·Select the motor code from the following table based on the power supply voltage of
the Inverter and the capacity of the motor.
Motor code
Power supply voltage
0
200 VAC
200 VAC
1
2
3
4
5
6
8
9
10
400 VAC
400 VAC
21
22
23
24
25
26
28
29
30
n140
Energy-saving Control
Coefficient K2
Setting
0.0 to 6,550
range
Note 1. The default setting varies with the capacity of the Inverter model.
Note 2. The constant automatically changes according to the motor code in n158. For
the fine-tuning of this parameter, set the motor code in advance.
Set Values
·When the output frequency is constant for a certain period while the Inverter is in effec-
tive energy-saving control, the Inverter is set to the primary level of energy-saving con-
trol by this parameter.
·Motor constants vary with the motor manufacturer. Therefore, the fine-tuning of the
parameter is required to find the ideal value. Fine-tune the parameter while the Inverter
is operating at constant frequency so that the output power will be minimum.
6-8
Motor capacity
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
4.0 kW
5.5 kW
7.5 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
4.0 kW
5.5 kW
7.5 kW
Register 018C
Hex
Unit of
0.1
setting
Chapter 6
Energy-saving
control coefficient K2
(n140)
481.7
356.9
288.2
223.7
169.4
156.8
156.8
122.9
94.8
72.7
713.8
576.4
447.4
338.8
313.6
245.8
245.8
189.5
145.4
Changes during
No
operation
Default setting
See
note 1