List of Parameters
Param-
Regis-
Name
eter
ter No.
No.
n038
0126
Motor protec-
tive time
n039
0127
Cooling fan
operation
n040
0128
Direction for
motor rotation
Description
Used to set the electric thermal char-
acteristics of the motor to be con-
nected in 1-minute increments.
Note The default setting does not
require any changes in normal
operation.
Note To set the parameter according
to the characteristics of the
motor, check with the motor
manufacturer the thermal time
constant and set the parameter
with some margin. In other
words, set the value slightly
shorter than the thermal time
constant.
Note To detect motor overloading
quicker, reduce the set value,
provided that it does not cause
any application problems.
Used to operate the Cooling Fan of
the Inverter while the Inverter is
turned ON or only while the Inverter is
in operation.
0: Rotates only while RUN command
is input and for 1 minute after
Inverter stops operating
1: Rotates while Inverter is turned ON
Note This parameter is available only
if the Inverter incorporates a
Cooling Fan.
Note If the operation frequency of the
Inverter is low, the life of the fan
can be prolonged by setting the
parameter to 0.
0: CCW
1: CW
The motor output shaft rotates in the
counterclockwise ('0") or in the clock-
wise ("1") direction with a forward in-
verter reference.
Note Applicable for software version
No. 010024 or later.
Chapter 10
Set-
Unit
Default
setting
ting
of
range
set-
ting
1 to 60 1 min
8
0, 1
1
0
0, 1
1
0
Changes
Ref-
during
er-
opera-
ence
tion
page
No
6-41
No
6-42
10-9

Hide quick links: