Omron SYSDRIVE 3G3MV User Manual page 210

Multi-function compact inverter sysdrive 3g3mv series
Hide thumbs Also See for SYSDRIVE 3G3MV:
Table of Contents

Advertisement

Communications
7-3-2 Data Write/Broadcast Data Write (Function Code: 10 Hex)
H Settings and Response
·To write data to the Inverter, such as control I/O and parameter set value data, issue the
following DSR message.
·Consecutive data of a maximum of 16 words (32 bytes for 16 registers) can be written
per DSR message.
·The register number is allocated to each function item, such as control I/O and param-
eter functions. The register number of each parameter is indicated wherever the
parameter is explained in this manual and in Section 10 List of Parameters. For regis-
ter numbers other than those of parameters, refer to 7-6 Register Number Allocations
in Details.
D DSR Message
Byte No.
1
Slave address
2
Function code (10 Hex)
3
Register No. of write start data
Register No. of write start data
4
5
No. of registers of write data (max. 16)
No. of registers of write data (max. 16)
6
7
Data of start register
Data of next register
Data of next register
8
9
10
Data of next register
Data of next register
11
12
Data of next register
Data of next register
13
:
CRC-16 check
CRC-16 check
n--1
n
7-16
Data
:
Chapter 7
MSB
LSB
MSB
LSB
MSB
LSB
: