Advanced Operation
Number of Fault Retries
n48
Setting
0 to 10
range
Set Values
Set the number of fault retries required.
The count of fault retries will be cleared in any of the following cases.
The Inverter is normal for 10 minutes continuously after the latest fault retry was
made.
Power supply to the Inverter is interrupted.
A fault reset is input.

6-7-5 Frequency Jump Function (n49 to n51)

The frequency jump function prevents the Inverter from generating frequencies that
make the mechanical system resonate.
The frequency jump function can be used effectively to set two dead bands of a fre-
quency reference.
Jump Frequency 1
n49
Setting
0.0 to 400 (Hz)
range
n50
Jump Frequency 2
Setting
0.0 to 400 (Hz)
range
Default Setting
n51
Setting
0.0 to 25.5 (Hz)
range
Note Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and
1-Hz increments if the frequency is 100 Hz or greater.
Unit of
1
setting
Unit of
0.1 Hz
setting
(see note)
Setting
0.1 Hz
range
(see note)
Unit of
0.1 Hz
setting
Chapter 6
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0.0
Changes during
No
operation
Unit of setting
0.0
Changes during
No
operation
Default setting
0.0
6-17