Electronic Thermal (Time Lag) - Daikin SkyAir GQI-Eco Series Service Manual

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013

4.24 Electronic Thermal (Time Lag)

L8
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
The error is detected from the current flowing to power transistor into voltage with CT1 (DC
current sensor).
Detection
Error Decision
When compressor overload (except for when startup) is detected.
Conditions
Supposed
Causes
Service Diagnosis
Disconnected compressor coil
High pressure is abnormal high
Defective compressor (if bearing is scratched)
Defective outdoor unit PCB
Stop valve is not opened
Troubleshooting by Remote Controller