Daikin SkyAir GQI-Eco Series Service Manual page 150

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

Troubleshooting by Remote Controller
A
CHECK 4
Continuity check in the power
transistor (IGBT). Is the
continuity normal?
YES
Turn the power ON, and then operate
the test operation.
Error is displayed again?
YES
Check the power supply voltage.
Is instantaneous
voltage drop generated?
NO
CHECK 4
Refer to P.170.
140
NO
NO
Continue the
operation normally.
YES
YES
Replace the outdoor unit PCB.
NO
Go to the other troubleshooting.
Normal operation.
Correct the power supply.
Compressor inspection.
Inspect according to the
diagnosis procedure for
abnormal noise, vibration,
operating status, etc. of the
compressor.
SiBE281013
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents