SiBE281013
3.2.6 Room Thermostat Control
Based on the difference between the set temperature by remote controller and indoor unit
suction air temperature, the thermo. is turned on and off.
∆
T = Indoor suction air temperature – temperature set by remote controller (Cooling)
∆
T = Temperature set by remote controller – indoor suction air temperature (Heating)
Thermostat ON Condition
∆
T > +0.5°C
Thermostat OFF Condition
Function and Control
• ∆T
≤
– 0.5˚C continues for 1 minute (for RZQG71LV1B)
• ∆T
≤
– 0.5˚C continues for 1 minute
• 5 minutes or more after start up
or
•&
(for RZQG100 - 140LV1B)
• ∆T
≤
– 2˚C (Cooling)
• ∆T
≤
– 2.5˚C (Heating)
When changed suddenly from ∆T
Function Details
≥
+1.5˚C to ∆T
≥
-0.5˚C
35