Daikin SkyAir GQI-Eco Series Service Manual page 45

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
3.2.6 Room Thermostat Control
Based on the difference between the set temperature by remote controller and indoor unit
suction air temperature, the thermo. is turned on and off.
T = Indoor suction air temperature – temperature set by remote controller (Cooling)
T = Temperature set by remote controller – indoor suction air temperature (Heating)
Thermostat ON Condition
T > +0.5°C
Thermostat OFF Condition
Function and Control
• ∆T
– 0.5˚C continues for 1 minute (for RZQG71LV1B)
• ∆T
– 0.5˚C continues for 1 minute
• 5 minutes or more after start up
or
•&
(for RZQG100 - 140LV1B)
• ∆T
– 2˚C (Cooling)
• ∆T
– 2.5˚C (Heating)
When changed suddenly from ∆T
Function Details
+1.5˚C to ∆T
-0.5˚C
35