Daikin SkyAir GQI-Eco Series Service Manual page 78

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

Field Setting from Remote Controller
Graph 2
Target evaporating temperature control when "low humidity application" is selected. Field
setting 16(26)-2-03:
Note:
Te by LP sensor
68
Te target acceptable area
Remote controller setting temp.
Te target
Te target limited ≤ 20˚C
(˚C)
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp. > setting → Te target down
Indoor temp. < setting → Te target up
RZQG Series
Te target limited ≥ 0˚C
Freeze protection
(40 min. integrated coil temp. ≤ -1˚C)
SiBE281013
Indoor Temp
(˚C DB)
Field Setting