Daikin SkyAir GQI-Eco Series Service Manual page 83

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
3.2.3 Setting Mode 2
In this mode, settings for the following items can be made.
No.
28
With this setting, compressor operation can be controlled to reduce power consumption.
(60% - 80% demand is available when a demand adapter (optional accessory) is used.)
[Work procedure]
Operating procedure
Push and hold the MODE (BS1) button of "Setting mode 1" for 5 seconds
or more and set to "Setting mode 2."
Push the SET (BS2) button three times to set the LED display as shown
in the table on the right.
Push the RETURN (BS3) button once. (Present settings are displayed.) k h h h h l h
Push the SET (BS2) button to set the LED
display as shown in the table on the right.
Push the RETURN (BS3) button once to make a
decision.
Push the RETURN (BS3) button once again for execution. (The LED
display is in the initial status of "Setting mode 2".)
Push the MODE (BS1) button once to return to Setting mode 1 (normal
operation).
Field Setting
Press the MODE (BS1) button for 5
seconds and set to "Setting mode 2".
<Selection of setting items>
Press the SET (BS2) button and set the
LED display to a setting item (∗1).
Press the RETURN (BS3) button and
decide the item.
∗ If you become unsure of how to proceed, push the MODE (BS1) button and return to setting mode 1.
Display of setting items
Setting item
H1P H2P H3P H4P H5P H6P H7P
k h h h h k k 30% demand
Demand 2
3
operation
k h k k k h h OFF (factory setting)
Refrigerant
recovery mode
The figures in the columns under "No." represent the number of times to push the
SET (BS2) button.
Setting of Demand 2 operation
Setting item
Demand 2 operation
LED display
Setting condition
40% demand (factory
setting)
50% demand
ON
Setting condition
30% demand
40% demand (factory setting) Operates with 40% of rated
50% demand
30% of rated power consumption
40% of rated power consumption
50% of rated power consumption
30% of rated power consumption
40% of rated power consumption
50% of rated power consumption
Field Setting from Outdoor Unit PCB
<Selection of setting conditions>
Press the SET (BS2) button and set to
the setting condition you want.
Press the RETURN (BS3) button and
decide the condition.
Press the RETURN (BS3) button and
set to the initial status of "Setting mode
2".
Display of setting condition
LED display
H1P H2P H3P H4P H5P H6P H7P
k h h h k h h
k h h h h k h
k h h h h h k
k h h h h h k
k h h h h k h
Description
Operates with 30% of rated
power consumption.
power consumption.
Operates with 50% of rated
power consumption.
h: OFF l: BLINK k: ON
H1P H2P H3P H4P H5P H6P H7P
k h h h h h h
k h h h h k k
k h h h l h h
k h h h h l h
k h h h h h l
k h h h k h h
k h h h h k h
k h h h h h k
k h h h h h h
h h h h h h h