Daikin SkyAir GQI-Eco Series Service Manual page 199

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
7. Charge hose for R-410A
8. Charging cylinder
Appendix
Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
Change in pressure
Change in service port diameter
Specifications
Working pressure 5.08 MPa (51.8 kg/cm
Rupture pressure 25.4 MPa (259 kg/cm
Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
Specifications
Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Precautions for New Refrigerant (R-410A)
(Hose with ball valve)
2
)
2
)
Can not be used
189