ESIE12-06
4.24 Electronic Thermal (Time Lag)
L8
Remote
Controller
Display
Applicable
RZQG
Models
Method of Error
The error is detected from the current flowing to power transistor into voltage with CT1 (DC
Detection
current sensor).
Error Decision
When compressor overload (except for when startup) is detected.
Conditions
Supposed
Disconnected compressor coil
Causes
High pressure is abnormal high
Defective compressor (if bearing is scratched)
Defective outdoor unit PCB
Stop valve is not opened
Service Diagnosis
Troubleshooting by Remote Controller
217