Daikin SkyAir GQI-Eco Series Service Manual page 46

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

Function Details
3.2.7 Compressor Step
The compressor operation frequency is controlled in order to keep a constant evaporation
temperature in cooling and a constant condensing temperature in heating.
Cooling
t cool = Remote controller set temperature - Indoor return air temperature.
Depending on ∆ t cool and the cooling load, the target evaporating temperature will be a value
between 2°C and 20°C.
Heating
t heat = Indoor return air temperature - Remote controller set temperature.
Depending on ∆ t heat and the heating load, the target condensing temperature will be a value
between 42°C and 54°C. (for RZQG100-140LV1B : 42°C and 50°C)
Step No.
36
RZQG71LV1B
1
2
3
57 Hz
4
61.5 Hz
5
66 Hz
6
72 Hz
7
78 Hz
8
85.5 Hz
9
93 Hz
10
102 Hz
11
109.5 Hz
12
118.5 Hz
13
127.5 Hz
14
136.5 Hz
15
145.5 Hz
16
151.5 Hz
17
154.5 Hz
18
174 Hz
19
183 Hz
20
192 Hz
21
201 Hz
22
211.5 Hz
23
222 Hz
24
232.5 Hz
25
243 Hz
26
253.5 Hz
27
265.5 Hz
28
277.5 Hz
29
289.5 Hz
: Maximum frequency in cooling
Compressor operation frequency
RZQG100LV1B
30 Hz
33 Hz
36 Hz
40 Hz
44 Hz
48 Hz
52 Hz
56 Hz
60 Hz
65 Hz
70 Hz
76 Hz
82 Hz
89 Hz
96 Hz
104 Hz
112 Hz
121 Hz
129 Hz
137 Hz
144 Hz
SiBE281013
RZQG125·140LV1B
30 Hz
33 Hz
36 Hz
40 Hz
44 Hz
48 Hz
52 Hz
56 Hz
60 Hz
65 Hz
70 Hz
76 Hz
82 Hz
89 Hz
96 Hz
104 Hz
112 Hz
121 Hz
129 Hz
137 Hz
144 Hz
151 Hz
159 Hz
167 Hz
175 Hz
180 Hz