Daikin SkyAir GQI-Eco Series Service Manual page 52

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

Function Details
3.2.17 Thermostat OFF due to Outdoor Air Temperature (Only in Heating
Operation)
If outdoor air temperature is high, the unit conducts forced thermostat OFF at the following
temperature to protect the system.
3.2.18 Inverter Current Protection Control
Restricts compressor operation frequency to prevent compressor from tripping due to inverter
overcurrent.
42
Outdoor air temperature > 32°C
Inverter current
> Stepping down current
Compressor frequency
–1 step/6 sec.
The condition of Inverter current < Stepping down current
continues for 2 minutes
Stepping-down
current A
OR
RZQG71LV1B
A
11.0 A
B
13.7 A
Normal operation
Compressor frequency
Outdoor heat exchanger temperature
(liquid) ≥ Indoor heat exchanger temperature
&
Outdoor heat exchanger temperature
(liquid) ≥ 25˚C
Outdoor heat exchanger temperature
(liquid) < Indoor heat exchanger temperature
Outdoor heat exchanger temperature
(liquid) < 25˚C
Inverter upper limit frequency
= Maximum frequency
+1 step/2 min.
Stepping-down
current B
RZQG100-140LV1B
14.0 A
20.0 A
Function and Control
SiBE281013