After Unit Shuts Down, It Cannot Be Restarted For A While - Daikin SkyAir GQI-Eco Series Service Manual

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

SiBE281013
2.5

After Unit Shuts Down, It cannot be Restarted for a While

Applicable Model
All models of SkyAir series
Supposed
Causes
Service Diagnosis
Overcurrent relay (for compressor)
Overcurrent relay may act due to the following reasons
Lower voltage of power supply
Excess level of high pressure
Insufficient size of power cable
Defective compressor
Compressor protection thermostat
Compressor protection thermostat may act due to the following reasons
Internal leakage of four way valve (There is no difference between suction and discharge
temperature)
Insufficient compression of compressor
Incorrect refrigerant
Defective electronic expansion valve
Insufficient circulation of refrigerant
Symptom-based Troubleshooting
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents