Daikin SkyAir GQI-Eco Series Service Manual page 152

Skyair gqi-eco rzqg71~140lv1b series heat pump r-410a 50hz
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be occurred.
Is the secondary
current of the inverter higher
than A (∗1) for
each phase?
NO
Turn OFF the power supply.
CHECK 4
Continuity check in the power
transistor (IGBT). Is the
continuity normal?
YES
Note:
1 Secondary electronic thermal detection value
Model
RZQG71
RZQG100-140
CHECK 2
Refer to P.168.
CHECK 4
Refer to P.170.
CHECK 9
Refer to P.174.
142
YES
Is the stop valve opened?
YES
CHECK 2
High pressure is high.
NO
NO
Detection value
Cooling
12.6 or 12.2A × 260 seconds
Heating
14.8A × 260 seconds
Cooling
16.1A × 260 seconds
Heating
22.1A × 260 seconds
NO
Open the stop valve.
YES
Remedy the cause.
Check for excessive refrigerant
charging.
CHECK 9
Replace the outdoor unit PCB
(A1P).
Replace the outdoor unit PCB
(A1P).
Compressor inspection.
Inspect according to the
diagnosis procedure for
abnormal noises, vibration,
operating status, etc. of the
compressor.
SiBE281013
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents