Motor brake and stop operation
(5) DC feeding mode 1 (Pr. 30 = "10, 11")
⋅ Setting "10, 11" in Pr. 30 enables DC power supply operation.
⋅ Leave the AC power supply connection terminal R/L1, S/L2, and T/L3 open and connect the DC power supply to
terminal P/+ and N/-. Also, remove jumpers across terminal R/L1-R1/L11 and S/L2-S1/L21, and connect terminals
R1/L11 and S1/L21 to terminal P/+ and N/-.
⋅ The diagram below is a connection example.
Frequency command
Frequency setting
200
DC power
MC
(+)
(-)
Forward rotation start
Reverse rotation start
Contact input common
3
2
potentiometer
1/2W1kΩ
1
Inverter
Inrush
R/L1
current
U
limit circuit
S/L2
V
T/L3
W
R1/L11
S1/L21
P/+
N/-
STF
STR
PC
10
2
5
IM
Earth
(Ground)