Monitor display and monitor output signal
(3) Torque monitoring reference (Pr. 866)
(10VDC)
(20mADC)
150% (initial value) 400%
Setting range of Pr. 866
(4) Terminal AM response adjustment (Pr. 867)
• Using Pr. 867, the output voltage response of the terminal AM can be adjusted within the range 0 to 5s.
• Increasing the setting stabilizes the terminal AM output more but reduces the response level. (Setting "0" sets the
response level to 4ms)
(5) Adjustment of response level of terminal CA (Pr. 869)
• The response level of the output current of the terminal CA can be adjusted between 0 and 5s with Pr. 869.
• Increasing the setting stabilizes the terminal CA output more but reduces the response level. (Setting "0" sets the
response level to about 7ms.)
250
• Set the current to be referenced when the torque monitor is selected
for the terminal CA and terminal AM display.
• Set the current value when the current output at terminal CA is
20mADC.
The analog current output and current value at terminal CA are
proportional. (The maximum output current is 20mADC.)
• Set the current value when the voltage output at terminal AM is
10VDC.
The analog voltage output and current value at terminal AM are
proportional. (The maximum output voltage is 10VDC.)