Control circuit specifications
2.3.5

When connecting the operation panel using a connection cable

When connecting the operation panel (FR-DU07) to the inverter using a cable, the operation panel can be mounted
on the enclosure surface and operationality improves.
Operation panel(FR-DU07)
REMARKS
· Overall wiring length when the operation panel is connected: 20m
· Refer to the following when fabricating the cable on the user side.
Commercially available product examples (as of Sep., 2006)
Product
1) 10BASE-T cable
2) RJ-45 connector
2.3.6
RS-485 terminal block
⋅ Conforming standard: EIA-485(RS-485)
⋅ Transmission format: Multidrop link
⋅ Communication speed: MAX 38400bps
⋅ Overall length: 500m
⋅ Connection cable:Twisted pair cable
(4 paires)
2.3.7

Communication operation

Using the PU connector or RS-485 terminal, you can perform communication operation from a personal computer
etc. When the PU connector is connected with a personal, FA or other computer by a communication cable, a user
program can run and monitor the inverter or read and write to parameters.
For the Mitsubishi inverter protocol (computer link operation), communication can be performed with the PU
connector and RS-485 terminal.
For the Modbus RTU protocol, communication can be performed with the RS-485 terminal.
For further details, refer to 315.
30
Parameter unit connection cable
(FR-CB2
)(option)
Operation panel connection connector
(FR-ADP)(option)
Type
SGLPEV-T 0.5mm × 4P
5-554720-3
Maker
Mitsubishi Cable Industries, Ltd.
Tyco Electronics Corporation
OPEN
Terminating resistor switch
Factory-set to "OPEN".
Set only the terminating resistor switch of
100Ω
the remotest inverter to the "100Ω" position.
RDA1
RDB1
RDA2
RDB2
(RXD1+)
(RXD1-)
(RXD2+)
(RXD2-)
SDA1
SDB1
SDA2
TXD
(TXD1+)
(TXD1-)
(TXD2+)
P5S
SG
P5S
(VCC)
(GND)
(VCC)
(GND)
RXD
SDB2
(TXD2-)
SG
VCC