Function Assignment Of External Terminal And Control; Input Terminal Function Selection (Pr. 178 To Pr. 189) - Mitsubishi Electric FR-A740-00023 Instruction Manual

Fr-a700 series
Table of Contents

Advertisement

Function assignment of external terminal and control

4.15 Function assignment of external terminal and control

Purpose
Assign function to input terminal
Set MRS signal (output shutoff) to
normally closed contact specification
Make the second (third) function
valid only during constant speed
operation
Assign start signal and forward/
reverse command to other signals
Assign function to output terminal
Detect output frequency
Detect output current
Remote output function
Detect output torque

4.15.1 Input terminal function selection (Pr. 178 to Pr. 189)

Use these parameters to select/change the input terminal functions.
Parameter
Number
178
STF terminal function selection
179
STR terminal function selection
180
RL terminal function selection
181
RM terminal function selection
182
RH terminal function selection
183
RT terminal function selection
184
AU terminal function selection
185
AM terminal function selection
186
CS terminal function selection
187
MRS terminal function selection
188
STOP terminal function selection
189
RES terminal function selection
(1) Input terminal function assignment
⋅ Use Pr. 178 to Pr. 189 to set the functions of the input terminals.
⋅ Refer to the following table and set the parameters:
Signal
Setting
Name
Pr. 59 = 0 (initial value)
0
RL
Pr. 59 = 1, 2
Pr. 270 = 1, 3
Pr. 59 = 0 (initial value)
1
RM
Pr. 59 = 1, 2
Pr. 59 = 0 (initial value)
2
RH
Pr. 59 = 1, 2
222
Input terminal function
selection
MRS input selection
RT reflection time selection
Start signal (STF/STR)
operation selection
Output terminal function
assignment
Up-to-frequency sensitivity
Output frequency detection
Low speed detection
Output current detection
Zero current detection
Remote output
Output torque detection
Initial
Name
Value
60
61
0
1
2
3
4
5
6
24
25
62
Function
Low-speed operation command
Remote setting (setting clear)
*1
Stop-on-contact selection 0
*2
Middle-speed operation command
Remote setting (deceleration)
*1
High-speed operation command
Remote setting (acceleration)
*1
Parameter that must be Set
Pr. 178 to Pr. 189
Pr. 190 to Pr. 196
Pr. 41 to Pr. 43, Pr. 50, Pr. 116,
Pr. 150 to Pr. 153, Pr. 166,
Pr. 495 to Pr. 497
Initial Signal
STF (forward rotation command)
STR (reverse rotation command)
RL (low-speed operation command)
RM (middle-speed operation command)
RH (high speed operation command)
RT (second function selection)
AU (terminal 4 input selection)
JOG (Jog operation selection)
CS (selection of automatic restart
after instantaneous power failure)
MRS (output stop)
STOP (start self-holding selection)
RES (inverter reset)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr. 270, Pr. 275, Pr. 276
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr.
232 to Pr. 239
Pr. 59
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Refer to Page
Pr. 17
Pr. 155
Pr. 250
Pr. 865
Pr. 167
Pr. 864
Setting Range
0 to 20, 22 to 28, 37, 42 to
44, 50, 60, 62, 64 to 71, 74,
9999
0 to 20, 22 to 28, 37, 42 to
44, 50, 61, 62, 64 to 71, 74,
9999
0 to 20, 22 to 28, 37, 42 to
44, 50, 62, 64 to 71, 74, 9999
0 to 20, 22 to 28, 37, 42 to
44, 50, 62 to 71, 74, 9999
0 to 20, 22 to 28, 37, 42 to
44, 50, 62, 64 to 71, 74, 9999
Related Parameters
222
225
226
227
230
237
239
241
240
Refer to
Page
160
164
205
160
164
160
164

Hide quick links: