Service Manual WNG LED/LCD Series Indoor Units Outdoor Units WNG 7 GCN 7 ONG 7 WNG 9 GCN 9 ONG 9 WNG 12 GCN 12 ONG 12 WNG 14 GC 14 ONG 14 WNG 18 GC 18 — WNG 21 GC 22 —...
Page 2
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Page 3
TABLE OF CONTENTS Table of Contents INTRODUCTION ....................1-1 PRODUCT DATA SHEET ..................2-1 RATING CONDITIONS ..................3-1 OUTLINE DIMENSIONS ..................4-1 PERFORMANCE DATA & PRESSURE CURVES ..........5-1 SOUND LEVEL CHARACTERISTICS ..............6-1 ELECTRICAL DATA ....................7-1 WIRING DIAGRAMS .....................8-1 ELECTRICAL CONNECTIONS ................9-1 10. REFRIGERATION DIAGRAMS ................10-1 11.
INTRODUCTION Indoor Unit The indoor unit is wall mounted, and can be easily fitted to many types of residential and commercials applications. It includes: Casing with air inlet and outlet grills. • A large-diameter tangential fan. • Bended coil with treated aluminum fins. •...
Service valves” flare” type connection. • Interconnecting wiring terminal block. • Fresh air motor for WNG 7-14 (optional). • Tubing Connections Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual, Chapter 9.
PRODUCT DATA SHEET PRODUCT DATA SHEET R410A Model Indoor Unit WNG-7 Model Outdoor Unit ONG-7 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 7610 7610 7760 Capacity 2.23 2.23 2.28 Power input 0.68 0.68 0.665 EER (Cooling) or COP(Heating) 3.28 3.28 3.42...
PRODUCT DATA SHEET Model Indoor Unit WNG-9 Model Outdoor Unit ONG-9 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 9280 9280 10240 Capacity 2.72 2.72 Power input 0.825 0.825 0.850 EER (Cooling) or COP(Heating) 3.30 3.30 3.53 Energy efficiency class Power supply...
Page 13
PRODUCT DATA SHEET Model Indoor Unit WNG-12 Model Outdoor Unit ONG-12 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 12390 12390 13650 Capacity 3.63 3.63 Power input 1.115 1.115 1.14 EER (Cooling) or COP(Heating) 3.26 3.26 3.51 Energy efficiency class Power supply...
Page 14
PRODUCT DATA SHEET Model Indoor Unit WNG-14 Model Outdoor Unit ONG-14 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 13650 13650 15290 Capacity 4.48 Power input 1.33 1.33 1.395 EER (Cooling) or COP(Heating) 3.01 3.01 3.21 Energy efficiency class Power supply V/Ph/Hz...
Page 15
PRODUCT DATA SHEET Model Indoor Unit WNG-18 Model Outdoor Unit GC-18 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 18250 18250 18420 Capacity (4) 5.35 5.35 5.40 Power input (4) 1.66 1.66 1.56 EER (Cooling) or COP(Heating) (4) 3.22 3.22 3.46...
Page 16
PRODUCT DATA SHEET Model Indoor Unit WNG 21 Model Outdoor Unit GC 21 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 21150 21150 22180 Capacity 6.50 Power input 2.05 2.05 2.00 EER (Cooling) or COP(Heating) 3.02 3.02 3.25 Energy efficiency class...
Page 17
PRODUCT DATA SHEET Model Indoor Unit WNG 24 Model Outdoor Unit OU7-24 Installation method WALL MOUNTED Characteristics Units Cooling only Cooling Heating Btu/hr 23100 23100 24150 Capacity (1) 6.77 6.77 7.08 Power input (1) 2.24 2.24 COP (1) 3.02 3.02 3.01 Energy efficiency class Power supply...
Page 18
PRODUCT DATA SHEET Model Indoor Unit WNG 24 Model Outdoor Unit OU7-24T Installation method WALL MOUNTED Characteristics Units Cooling only Cooling Heating Btu/hr 23220 23220 25130 Capacity (1) 6.81 6.81 7.37 Power input (1) 2.26 2.26 COP (1) 3.01 3.01 3.07 Energy efficiency class Power supply...
Page 19
PRODUCT DATA SHEET Model Indoor Unit WNG-25 Model Outdoor Unit GC-24 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 22960 22960 24570 Capacity 6.73 6.73 Power input 2.34 2.34 2.33 EER (Cooling) or COP(Heating) 2.88 2.88 3.09 Energy efficiency class Power supply...
Page 20
PRODUCT DATA SHEET Model Indoor Unit WNG- 30 Model Outdoor Unit OU8-30 R410A Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 29000 29000 31800 Capacity 9.08 Power input 2.92 2.92 2.98 EER (Cooling) or COP(Heating) 2.91 2.91 3.05 Energy efficiency class...
Page 21
PRODUCT DATA SHEET Model Indoor Unit WNG- 30T Model Outdoor Unit OU8-30T R410A Installation Method of Pipe WALL MOUNTED Characteristics Units Cooling Only Cooling Heating Btu/hr 29000 29000 31000 Capacity 9.08 Power input 2.83 2.83 2.98 EER (Cooling) or COP(Heating) 3.00 3.00 3.05...
Page 22
PRODUCT DATA SHEET Model Indoor Unit WNG 36 Model Outdoor Unit OU10-36 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 34600 34600 38000 Capacity 10.15 10.15 11.14 Power input 3.22 3.22 3.60 EER (Cooling) or COP(Heating) 3.15 3.15 3.10...
Page 23
PRODUCT DATA SHEET Model Indoor Unit WNG 36 Model Outdoor Unit OU10-36T Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 35480 35480 38200 Capacity 10.40 10.40 11.20 Power input 3.06 3.06 3.40 EER (Cooling) or COP(Heating) 3.40 3.40 3.30...
Page 24
PRODUCT DATA SHEET R407C Model Indoor Unit WNG-7 Model Outdoor Unit GCN-7 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 7710 7710 7610 Capacity 2.26 2.26 2.23 Power input 0.690 EER (Cooling) or COP(Heating) 2.83 2.83 3.23 Energy efficiency class Power supply...
Page 25
PRODUCT DATA SHEET Model Indoor Unit WNG-9 Model Outdoor Unit ONG3-9 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 9280 9080 10200 Capacity 2.72 2.66 2.99 Power input 0.88 0.920 EER (Cooling) or COP(Heating) 3.02 3.02 3.25 Energy efficiency class Power supply...
Page 26
PRODUCT DATA SHEET Model Indoor Unit WNG-12 Model Outdoor Unit ONG3-12 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 12390 12390 13000 Capacity 3.63 3.63 3.81 Power input 1.180 EER (Cooling) or COP(Heating) 3.03 3.03 3.23 Energy efficiency class Power supply V/Ph/Hz...
Page 27
PRODUCT DATA SHEET Model Indoor Unit WNG-14 Model Outdoor Unit ONG3-14 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 14190 14190 14880 Capacity 4.16 4.16 4.36 Power input 1.46 1.46 1.540 EER (Cooling) or COP(Heating) 2.85 2.85 2.83 Energy efficiency class...
Page 28
PRODUCT DATA SHEET Model Indoor Unit WNG- 30 Model Outdoor Unit OU833 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 30000 30000 32910 Capacity 9.64 Power input 3.38 3.38 3.88 EER (Cooling) or COP(Heating) Energy efficiency class Power supply V/Ph/Hz 220-240V/Single/50Hz...
Page 29
PRODUCT DATA SHEET Model Indoor Unit WNG-30 Model Outdoor Unit OU830T Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 29810 29810 31270 Capacity 8.73 8.73 9.16 Power input 3.33 EER (Cooling) or COP(Heating) 2.56 2.56 2.75 Energy efficiency class Power supply V/Ph/Hz...
Page 30
PRODUCT DATA SHEET Model Indoor Unit WNG-7 Model Outdoor Unit GCN-7 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 7710 7710 7610 Capacity 2.27 2.27 2.32 Power input 0.680 EER (Cooling) or COP(Heating) 2.84 2.84 3.41 Energy efficiency class Power supply V/Ph/Hz...
Page 31
PRODUCT DATA SHEET Model Indoor Unit WNG-9 Model Outdoor Unit GCN-9 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 9550 9080 10200 Capacity 2.80 2.83 Power input 0.99 0.99 0.920 EER (Cooling) or COP(Heating) 2.83 2.83 3.08 Energy efficiency class Power supply...
Page 32
PRODUCT DATA SHEET Model Indoor Unit WNG-9 Model Outdoor Unit ONG3-9 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 9690 9080 10200 Capacity 2.84 2.84 2.90 Power input 0.93 0.93 0.900 EER (Cooling) or COP(Heating) 3.05 3.05 3.22 Energy efficiency class...
Page 33
PRODUCT DATA SHEET Model Indoor Unit WNG-12 Model Outdoor Unit GCN-12 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 12280 12280 13000 Capacity 3.72 Power input 1.25 1.25 1.27 EER (Cooling) or COP(Heating) 2.88 2.88 2.93 Energy efficiency class Power supply V/Ph/Hz...
Page 34
PRODUCT DATA SHEET Model Indoor Unit WNG-12 Model Outdoor Unit ONG3-12 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 12280 12280 13000 Capacity 3.60 3.72 Power input 1.23 1.23 1.230 EER (Cooling) or COP(Heating) 2.93 2.93 3.02 Energy efficiency class Power supply...
Page 35
PRODUCT DATA SHEET Model Indoor Unit WNG-14 Model Outdoor Unit GC-14 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 14190 14190 14880 Capacity 4.12 4.12 4.75 Power input 1.65 1.65 1.690 EER (Cooling) or COP(Heating) 2.50 2.50 2.81 Energy efficiency class...
Page 36
PRODUCT DATA SHEET Model Indoor Unit WNG-14 Model Outdoor Unit ONG3-14 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 14190 14190 14880 Capacity Power input 1.55 1.55 1.67 EER (Cooling) or COP(Heating) 2.71 2.71 2.81 Energy efficiency class Power supply V/Ph/Hz 230V/50Hz/Single...
Page 37
PRODUCT DATA SHEET Model Indoor Unit WNG-25 Model Outdoor Unit GC-24 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 24050 24050 24230 Capacity 7.05 7.05 Power input 2.51 2.51 2.35 EER (Cooling) or COP(Heating) 2.81 2.81 3.02 Energy efficiency class Power supply...
Page 38
PRODUCT DATA SHEET Model Indoor Unit WNG-30 Model Outdoor Unit GC-30 Installation Method of Pipe Flared Characteristics Units cooling only Cooling Heating Btu/hr 29000 29000 32410 Capacity Power input 3.25 EER (Cooling) or COP(Heating) 2.74 2.74 2.92 Energy efficiency class Power supply V/Ph/Hz 230V/Single/50Hz...
Page 39
PRODUCT DATA SHEET Model Indoor Unit WNG- 30 Model Outdoor Unit OU830 Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 30000 30000 29500 Capacity 8.65 Power input EER (Cooling) or COP(Heating) 2.75 2.75 2.65 Energy efficiency class Power supply V/Ph/Hz 220-240V/Single/50Hz...
Page 40
PRODUCT DATA SHEET Model Indoor Unit WNG-30 Model Outdoor Unit OU830T Installation Method of Pipe Flared Characteristics Units Cooling Only Cooling Heating Btu/hr 30000 30000 30000 Capacity Power input EER (Cooling) or COP(Heating) Energy efficiency class Power supply V/Ph/Hz 400V/3PH/50Hz Rated current Starting current Circuit breaker rating...
RATING CONDITIONS RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: C DB 19 C WB Outdoor: 35 C DB Heating: Indoor: C DB Outdoor: 7 C DB 6 C WB Operating Limits 3.1.1 R410A Indoor...
Page 47
PERFORMANCE DATA & PRESSURE CURVES PERFORMANCE DATA & PRESSURE CURVES WNG7 ONG7 R410A 5.1.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27...
Page 48
PERFORMANCE DATA & PRESSURE CURVES 5.1.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL ( °C) 1.20 0.54 1.15 0.57 1.11 0.60 1.29 0.55 1.24 0.58...
Page 50
PERFORMANCE DATA & PRESSURE CURVES 5.3.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB Revision Y05-03 Service Manual - WNG CONTENT...
Page 51
PERFORMANCE DATA & PRESSURE CURVES WNG9 ONG9 R410A 5.4.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29 23/32 2.87 2.97...
Page 52
PERFORMANCE DATA & PRESSURE CURVES 5.4.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 1.58 0.68 1.52 0.72 1.46 0.76 1.70 0.70 1.64 0.74 1.58...
Page 54
PERFORMANCE DATA & PRESSURE CURVES 5.6.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB Revision Y05-03 Service Manual - WNG CONTENT...
Page 55
PERFORMANCE DATA & PRESSURE CURVES WNG12 ONG12 R410A 5.7.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29 23/32 3.83 3.96...
Page 56
PERFORMANCE DATA & PRESSURE CURVES 5.7.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 2.10 0.91 2.02 0.97 1.94 1.02 2.26 0.93 2.18 0.99 2.10...
Page 58
PERFORMANCE DATA & PRESSURE CURVES 5.9.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-12 Revision Y05-03 Service Manual - WNG...
Page 59
PERFORMANCE DATA & PRESSURE CURVES 5.10 WNG14 ONG14 R410A 5.10.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 4.22...
Page 60
PERFORMANCE DATA & PRESSURE CURVES 5.10.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 2.35 1.12 2.26 1.19 2.17 1.25 2.53 1.15 2.44 1.21 2.35...
Page 62
PERFORMANCE DATA & PRESSURE CURVES 5.12.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-16 Revision Y05-03 Service Manual - WNG...
Page 63
PERFORMANCE DATA & PRESSURE CURVES 5.13 WNG18 GC18 R410A 5.13.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29 23/32 5.64...
Page 64
PERFORMANCE DATA & PRESSURE CURVES 5.13.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL ( °C) 2.84 1.25 2.73 1.33 2.62 1.40 3.05 1.28 2.94 1.35...
Page 66
PERFORMANCE DATA & PRESSURE CURVES 5.15.2 Heating. Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB 5-20 Revision Y05-03 Service Manual - WNG...
Page 67
PERFORMANCE DATA & PRESSURE CURVES 5.16 WNG21 GC21 R410A 5.16.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29 23/32 6.53...
Page 68
PERFORMANCE DATA & PRESSURE CURVES 5.16.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL ( °C) 3.41 1.60 3.28 1.70 3.15 1.79 3.67 1.64 3.54 1.73...
Page 69
PERFORMANCE DATA & PRESSURE CURVES 5.18 Pressure Curves. 5.18.1 Cooling. 5-23 Service Manual - WNG Revision Y05-03 CONTENT...
Page 70
PERFORMANCE DATA & PRESSURE CURVES 5.18.2 Heating. 5-24 Revision Y05-03 Service Manual - WNG CONTENT...
Page 71
PERFORMANCE DATA & PRESSURE CURVES 5.19 WNG24 OU7- 24 1PH/3PH R410A 5.19.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29...
Page 72
PERFORMANCE DATA & PRESSURE CURVES 5.19.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL ( °C) 4.09 1.92 3.93 2.04 3.78 6.34 4.40 1.97 4.24 2.08...
Page 74
PERFORMANCE DATA & PRESSURE CURVES 5.21.2 Heating. Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB 5-28 Revision Y05-03 Service Manual - WNG CONTENT...
Page 75
PERFORMANCE DATA & PRESSURE CURVES 5.22 WNG25 GC24 R410A 5.22.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 7.09...
Page 76
PERFORMANCE DATA & PRESSURE CURVES 5.22.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL ( °C) 3.78 1.86 3.64 1.99 3.49 2.09 4.07 1.91 3.92 2.02...
Page 78
PERFORMANCE DATA & PRESSURE CURVES 5.24.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-32 Revision Y05-03 Service Manual - WNG...
Page 79
PERFORMANCE DATA & PRESSURE CURVES 5.25 WNG30 OU830 R410A 5.25.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 8.96...
Page 80
PERFORMANCE DATA & PRESSURE CURVES 5.25.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 4.77 2.38 4.59 2.54 4.40 2.67 5.13 2.44 4.95 2.58 4.77...
Page 82
PERFORMANCE DATA & PRESSURE CURVES 5.27.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-36 Revision Y05-03 Service Manual - WNG...
Page 83
PERFORMANCE DATA & PRESSURE CURVES 5.28 WNG30 OU830T R410A 5.28.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 8.96...
Page 84
PERFORMANCE DATA & PRESSURE CURVES 5.28.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 4.77 2.38 4.59 2.54 4.40 2.67 5.13 2.44 4.95 2.58 4.77...
Page 86
PERFORMANCE DATA & PRESSURE CURVES 5.30.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 12.0 11.0 10.0 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-40 Revision Y05-03 Service Manual - WNG...
Page 87
PERFORMANCE DATA & PRESSURE CURVES 5.31 WNG 36 OU10- 36 R410A 5.31.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29...
Page 88
PERFORMANCE DATA & PRESSURE CURVES 5.31.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 5.99 2.88 5.76 3.07 5.53 3.22 6.44 2.95 6.21 3.11 5.99...
Page 89
PERFORMANCE DATA & PRESSURE CURVES 5.33 Pressure Curves. 5.33.1 Cooling. 5-43 Service Manual - WNG Revision Y05-03 CONTENT...
Page 90
PERFORMANCE DATA & PRESSURE CURVES 5.33.2 Heating. 5-44 Revision Y05-03 Service Manual - WNG CONTENT...
Page 91
PERFORMANCE DATA & PRESSURE CURVES 5.34 WNG 36 OU10- 36T R410A 5.34.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL (°C) 15/21 17/24 19/27 21/29...
Page 92
PERFORMANCE DATA & PRESSURE CURVES 5.34.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 5.88 2.72 5.66 2.90 5.43 3.04 6.33 2.79 6.10 2.94 5.88...
Page 93
PERFORMANCE DATA & PRESSURE CURVES 5.36 Pressure Curves. 5.36.1 Cooling. 5-47 Service Manual - WNG Revision Y05-03 CONTENT...
Page 94
PERFORMANCE DATA & PRESSURE CURVES 5.36.2 Heating. 5-48 Revision Y05-03 Service Manual - WNG CONTENT...
Page 95
PERFORMANCE DATA & PRESSURE CURVES 5.37 WNG7 GCN7 R407C 5.37.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 2.38...
Page 96
PERFORMANCE DATA & PRESSURE CURVES 5.372.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERNING AIR WB OU COIL (ºC) 1.17 0.55 1.13 0.59 1.08 0.62 1.26 0.57 1.22 0.60 1.17...
Page 98
PERFORMANCE DATA & PRESSURE CURVES 5.39.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-52 Revision Y05-03 Service Manual - WNG CONTENT...
Page 99
PERFORMANCE DATA & PRESSURE CURVES 5.40 WNG9 ONG9 R407C 5.40.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 2.87...
Page 100
PERFORMANCE DATA & PRESSURE CURVES 5.40.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 1.57 0.74 1.51 0.79 1.45 0.83 1.69 0.76 1.63 0.80 1.57...
Page 102
PERFORMANCE DATA & PRESSURE CURVES 5.42.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-56 Revision Y05-03 Service Manual - WNG CONTENT...
Page 103
PERFORMANCE DATA & PRESSURE CURVES 5.43 WNG12 ONG12 R407C 5.43.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 3.83...
Page 104
PERFORMANCE DATA & PRESSURE CURVES 5.43.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 2.00 0.94 1.92 1.01 1.85 1.06 2.15 0.97 2.08 1.02 2.00...
Page 106
PERFORMANCE DATA & PRESSURE CURVES 5.45.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-60 Revision Y05-03 Service Manual - WNG CONTENT...
Page 107
PERFORMANCE DATA & PRESSURE CURVES 5.46 WNG14 ONG14 R407C 5.46.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 4.38...
Page 108
PERFORMANCE DATA & PRESSURE CURVES 5.46.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 2.29 1.23 2.20 1.31 2.11 1.38 2.46 1.26 2.38 1.33 2.29...
Page 110
PERFORMANCE DATA & PRESSURE CURVES 5.48.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-64 Revision Y05-03 Service Manual - WNG CONTENT...
Page 111
PERFORMANCE DATA & PRESSURE CURVES 5.49 WNG30 OU8-33 R407C 5.49.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 9.28...
Page 112
PERFORMANCE DATA & PRESSURE CURVES 5.49.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 5.06 3.10 4.87 3.31 4.68 3.47 5.45 3.18 5.25 3.36 5.06...
Page 114
PERFORMANCE DATA & PRESSURE CURVES 5.51.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-68 Revision Y05-03 Service Manual - WNG CONTENT...
Page 115
PERFORMANCE DATA & PRESSURE CURVES 5.52 WNG30 OU8-33T R407C 5.52.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 9.20...
Page 116
PERFORMANCE DATA & PRESSURE CURVES 5.52.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 4.81 2.66 4.63 2.84 4.44 2.98 5.18 2.73 4.99 2.88 4.81...
Page 118
PERFORMANCE DATA & PRESSURE CURVES 5.54.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-72 Revision Y05-03 Service Manual - WNG CONTENT...
Page 119
PERFORMANCE DATA & PRESSURE CURVES 5.55 WNG7 GCN7 R22 5.55.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 2.39...
Page 120
PERFORMANCE DATA & PRESSURE CURVES 5.55.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 1.22 0.54 1.17 0.58 1.13 0.61 1.31 0.56 1.26 0.59 1.22...
Page 122
PERFORMANCE DATA & PRESSURE CURVES 5.57.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-76 Revision Y05-03 Service Manual - WNG CONTENT...
Page 123
PERFORMANCE DATA & PRESSURE CURVES 5.58 WNG9 GCN9 R22 5.58.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 2.95...
Page 124
PERFORMANCE DATA & PRESSURE CURVES 5.58.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OD COIL (°C) 1.49 0.74 1.43 0.78 1.37 0.82 1.60 0.75 1.54 0.80 1.49...
Page 126
PERFORMANCE DATA & PRESSURE CURVES 5.60.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-80 Revision Y05-03 Service Manual - WNG CONTENT...
Page 127
PERFORMANCE DATA & PRESSURE CURVES 5.61 WNG12 GCN12 R22 5.61.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 3.79...
Page 128
PERFORMANCE DATA & PRESSURE CURVES 5.61.2 15.46.3 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OD COIL (°C) 1.95 1.02 1.88 1.08 1.80 1.14 2.10 1.04 2.03 1.10...
Page 130
PERFORMANCE DATA & PRESSURE CURVES 5.63.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-84 Revision Y05-03 Service Manual - WNG CONTENT...
Page 131
PERFORMANCE DATA & PRESSURE CURVES 5.64 WNG14 GCN14 R22 5.64.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 4.34...
Page 132
PERFORMANCE DATA & PRESSURE CURVES 5.64.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 2.49 1.35 2.40 1.44 2.30 1.51 2.68 1.39 2.59 1.46 2.49...
Page 134
PERFORMANCE DATA & PRESSURE CURVES 5.66.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-88 Revision Y05-03 Service Manual - WNG CONTENT...
Page 135
PERFORMANCE DATA & PRESSURE CURVES 5.67 WNG9 ONG9 R22 5.67.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 2.99...
Page 136
PERFORMANCE DATA & PRESSURE CURVES 5.67.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 1.52 0.72 1.46 0.77 1.41 0.81 1.64 0.74 1.58 0.78 1.52...
Page 138
PERFORMANCE DATA & PRESSURE CURVES 5.69.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-92 Revision Y05-03 Service Manual - WNG CONTENT...
Page 139
PERFORMANCE DATA & PRESSURE CURVES 5.70 WNG12 ONG12 R22 5.70.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 3.79...
Page 140
PERFORMANCE DATA & PRESSURE CURVES 5.69.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 1.95 0.98 1.88 1.05 1.80 1.10 2.10 1.01 2.03 1.06 1.95...
Page 142
PERFORMANCE DATA & PRESSURE CURVES 5.71.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-96 Revision Y05-03 Service Manual - WNG CONTENT...
Page 143
PERFORMANCE DATA & PRESSURE CURVES 5.72 WNG14 ONG14 R22 5.72.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 4.43...
Page 144
PERFORMANCE DATA & PRESSURE CURVES 5.72.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL ( °C) 2.47 1.34 2.37 1.42 2.28 1.49 2.66 1.37 2.56 1.44...
Page 146
PERFORMANCE DATA & PRESSURE CURVES 5.74.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-100 Revision Y05-03 Service Manual - WNG CONTENT...
Page 147
PERFORMANCE DATA & PRESSURE CURVES 5.75 WNG25 GC24 R22 5.75.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 7.38...
Page 148
PERFORMANCE DATA & PRESSURE CURVES 5.75.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 3.73 1.88 3.59 2.00 3.44 2.10 4.01 1.93 3.87 2.03 3.73...
Page 150
PERFORMANCE DATA & PRESSURE CURVES 5.77.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-104 Revision Y05-03 Service Manual - WNG CONTENT...
Page 151
PERFORMANCE DATA & PRESSURE CURVES 5.78 WNG30 GC30 R22 5.78.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 8.96...
Page 152
PERFORMANCE DATA & PRESSURE CURVES 5.78.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) INTERING AIR WB OU COIL (ºC) 4.99 2.60 4.80 2.77 4.61 2.91 5.37 2.67 5.18 2.81 4.99...
Page 154
PERFORMANCE DATA & PRESSURE CURVES 5.80.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-108 Revision Y05-03 Service Manual - WNG CONTENT...
Page 155
PERFORMANCE DATA & PRESSURE CURVES 5.81 WNG30 OU830 R22 5.81.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 9.28...
Page 156
PERFORMANCE DATA & PRESSURE CURVES 5.81.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 4.54 2.64 4.37 2.81 4.20 2.95 4.89 2.71 4.71 2.85 4.54...
Page 158
PERFORMANCE DATA & PRESSURE CURVES 5.83.2 Heating. Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB Suction Pressure VS.Outdoor Temp 15 DB (ºC) 20 DB (ºC) 25 DB (ºC) Outdoor Temp.( WB 5-112 Revision Y05-03 Service Manual - WNG CONTENT...
Page 159
PERFORMANCE DATA & PRESSURE CURVES 5.84 WNG30 OU833T R22 5.84.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR WB/DB ID COIL ( °C) ENTERING AIR DATA DB OU COIL( °C) 15/21 17/24 19/27 21/29 23/32 9.28...
Page 160
PERFORMANCE DATA & PRESSURE CURVES 5.84.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL ( °C) ENTERING AIR WB OU COIL (°C) 4.62 2.40 4.44 2.56 4.27 2.69 4.97 2.46 4.80 2.60 4.62...
ELECTRICAL DATA ELECTRICAL DATA Single and Three Phase Units MODEL WNG7 LED / LCD WNG9 LED / LCD WNG12 LED / LCD WNG14 LED / LCD To indoor To indoor To indoor To indoor Power Supply 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz 1PH-230V-50Hz Max Current, (A) Circuit Breaker,(A) Power Supply Wiring.
WIRING DIAGRAMS WIRING DIAGRAMS NOTE Wiring diagram lables as shown on units. Indoor Unit WNG7,9,12,14 LED Indoor Unit WNG7,9,12,14 LCD Service Manual - WNG Revision Y05-03 CONTENT...
Page 167
WIRING DIAGRAMS Indoor Unit WNG 18, 24, LED DISPLAY EMERG MOTOR P.C.B S.ICT CLOCK ROOM COMP LINE OF RV 220-240V 50HZ STEP MOTOR E.S.F IONIZER LEGEND Y/G--YELLOW/GREEN CABLE BETWEEN INDOOR BR---BROWN AND OUTDOOR UNITS BK---BLACK BU---BLUE HEAT PUMP 5X1.5MM (WNG18) GY---GRAY 5X2.5MM (WNG24)
Page 168
WIRING DIAGRAMS Indoor Unit WNG 25,30, 36 Outdoor Unit GCN 7,9,12 1PH R407/R22 GC 14 1PH R407/R22 Service Manual - WNG Revision Y05-03 CONTENT...
Page 169
WIRING DIAGRAMS Outdoor Unit GC 18 1PH R410A Outdoor Unit GC 24 1PH R410A/R407C/R22 Revision Y05-03 Service Manual - WNG CONTENT...
Page 170
WIRING DIAGRAMS Outdoor Unit GC 30 1PH R22 8.10 Outdoor Unit ONG 7 1PH R410A Service Manual - WNG Revision Y05-03 CONTENT...
Page 171
WIRING DIAGRAMS 8.11 Outdoor Unit ONG 9, 12, 14 1PH R407C/R22 8.12 Outdoor Unit OU7-24/OU8-30 1PH R410A Revision Y05-03 Service Manual - WNG CONTENT...
Page 172
WIRING DIAGRAMS 8.13 Outdoor Unit OU7-24/OU8-30 3PH R410A 8.14 Outdoor Unit OU8-33 3PH R410A, R407C/R22 Service Manual - WNG Revision Y05-03 CONTENT...
Page 173
WIRING DIAGRAMS 8.13 Outdoor Unit OU8-33 3PH R410A/R407C/R22 Revision Y05-03 Service Manual - WNG CONTENT...
CONTROL SYSTEM CONTROL SYSTEM WNG 7-14 LED TYPE UNITS 12.1 Electronic Control 12.1.1 Introduction The electronic control information is designed for service applications, and is common to the following groups of air-conditioners: • ST/ RC group -Cooling only / cooling and heating by heat pump.
Page 187
CONTROL SYSTEM 12.2 Legend - Alternate Current - Air-Conditioner - ON or OFF status CLOCK - ON/OFF Operation Input, (dry contact) COMP - Compressor - Central Processing Unit ELUM - Extended Louver Upward Movement (Software Jumper) E²PROM, EEP - Erase Enable Programmable Read Only Memory - Heating Element - High Pressure Control - Hardware...
Page 188
CONTROL SYSTEM 12.3 Main PCB Controller 12.3.1 LED Display WNG 7-14 OPR’(STBY’RED;ON:GREEN) RECIVER FRESH AIR TIMER FILTER LED 12-3 Service Manual - WNG Revision Y05-03 CONTENT...
CONTROL SYSTEM 12.4 General functions 12.4.1 COMP operation For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting, excluding DEICING Mode The Min operation time of COMP under different operating conditions is Min operation time of Operation Mode COMP...
Page 190
CONTROL SYSTEM 12.4.5 Protections • High pressure protection is applicable to all operating modes. • Deicing control is valid in Heat and Auto Heat Mode only. • Defrosting control is valid in Dry, Cool, Heat and Auto Modes. • No reset after protection modes. 12.4.6 Thermistors operation •...
Page 191
CONTROL SYSTEM 12.4.6.2 Cases for disabling thermistor short/disconnected detection The detection of thermistor faults (a) and (b) above, are disabled when Deicer Protection is started. The detection will be enabled again only after (1) the deicing is completed, and (2) COMP has been restarted and operated for 30 sec.
Page 192
CONTROL SYSTEM 12.5 Cooling Mode - General Room Temperature, RT, is detected by • RAT in normal operation, or • RCT (R/C sensor) in I-FEEL mode. The resolution of RT is 1 • RT is activating COMP/WVL if (RT > SPT), and •...
Page 193
CONTROL SYSTEM 12.5.1 Cooling Mode: Cool, Auto (at Cooling) Temp: Selected desired temperature. Fan: HIGH, MED, LOW Timer: Any I Feel: On or Off Control function Maintains room temp at desired level by comparing RT and SPT. (RT - SPT) [ COMP (WVL) OFAN...
Page 194
CONTROL SYSTEM 12.5.2 Cooling with Autofan Mode: Cool, Auto (at cooling) Temp: Selected desired temperature Fan: Auto Timer: Any I Feel: On or Off Control function Maintains room temp at desired level and controls the IFAN speed for optimal comfort. (RT - SPT) [ COMP (WVL)
CONTROL SYSTEM 12.6 Heating Mode 12.6.1 Heating Mode - General • In heating Mode, temp. compensation schedule will be activated for wall mounted units. Add to SPT SPT [ I-FEEL ON I-FEEL OFF 18 ≤ SPT ≤ 27 27 < SPT ≤ 30 Notes : •...
Page 196
CONTROL SYSTEM 12.6.3 HE operation • For all Groups, HE can be ON only when IFAN is ON. • For all Groups, HE switches to OFF when ICT > 50 c, and is activated again when ICT ≤ 45 • In SH or RC group, HE operation is limited by the following graph: General : ICT [...
Page 197
CONTROL SYSTEM 12.6.4 Heating, RC or SH Group Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: HIGH, MED, LOW Timer: Any I Feel: On or Off Control function Maintains room temp. at desired level by comparing RAT or RCT to SPT. (RT - SPT) [ COMP (WVL)
Page 198
CONTROL SYSTEM 12.6.5 Heating, RC or SH Group with Autofan Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: Auto Timer: Any I Feel: On or Off Control function Maintains room temp at desired level by controlling COMP, IFAN and OFAN. (RT - SPT) [ COMP (WVL)
Page 199
CONTROL SYSTEM 12.6.6 OFAN operation is controlled by the graph below when 1. (RAT ≥ SPT – 2 c), AND 2. (ICT ≥ 45 c), AND 3. (COMP is ON) Otherwise, OFAN runs together with COMP. OCT [ OFAN 12-14 Revision Y05-03 Service Manual - WNG CONTENT...
Page 200
CONTROL SYSTEM 12.7 Automatic Cooling or Heating 12.7.1 Automatic Cooling or Heating - General • Switching-temperature between Cooling and Heating is SPT ± 3 • Autofan in Automatic Cooling and Heating Mode will activate “Cooling with Autofan Mode” and “Heating with Autofan Mode” respectively. •...
Page 201
CONTROL SYSTEM 12.7.2 Auto Cooling or Heating, RC or SH Groups Mode: Auto Temp: Selected desired temperature Fan: Timer: Any I Feel: On or Off Control function Maintains room temp at desired level by selecting between cooling and heating modes. (RT - SPT) [ Auto Heat Mode Auto Cool Mode...
CONTROL SYSTEM 12.8 Dry Mode 12.8.1 Dry, ST or RC group Mode: Dry Temp: Selected desired temp Fan: Low (automatically selected by software) Timer: Any I FEEL: Control function Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with low speed IFAN.
Page 203
CONTROL SYSTEM 12.9 Protection 12.9.1 Cooling Mode Protections Indoor Coil Defrost Mode: Cooling, Dry, Auto Temp: Selected desired temp. Fan: Timer: Any I Feel: On or Off Control Function Protect the indoor coil from ice formation at low ambient temperature. ICT [ OFAN COMP...
Page 204
CONTROL SYSTEM 12.3.2 High Pressure Protection Mode: (Auto) Cooling or Dry Temp: Selected desired temp. Fan: Timer: Any I Feel: On or Off Control Function To protect the COMP from the high pressure built-up in the outdoor coil during normal cooling operation, by switching OFF the IFAN and COMP.
Page 205
CONTROL SYSTEM 12.9.3 Heating Mode Protections Outdoor coil Deicing (excluding RH Group) Mode: Heating, Auto (at heating) Temp: Selected desired Temp Fan: Timer: Any I FEEL: Control function Protects the Outdoor coil from ice formation by controlling COMP & RV operation. Scope This new deicer is designed to operate at extreme temp conditions.
Page 206
CONTROL SYSTEM Deicing procedure OCT [ (DDT) 3 min 3 min max 12 min. COMP DI (note 1) DI (note 2) OFAN IFAN is forced to Low Speed IFAN HEs are forced ON IFAN Note 3 HEs are forced OFF OPER BLINK Notes :...
Page 207
CONTROL SYSTEM 12.9.4 High pressure protection (excluding RH Group) Mode: (Auto) Heating Fan: Timer: Any I Feel: On or Off Control Function Protect the Compressor from high pressure by switching OFF the OFAN and COMP. ICT [ For all models except WAX For WAX model COMP COMP is forced OFF...
Page 208
CONTROL SYSTEM 12.10 Timer Mode: Any Temp. Selected desired temp Fan: Timer: Timer On, Timer Off I Feel: On or Off Control function • Starts or stops the unit operation after pre-set time. If RC-1 is used, the timer setting will be (0.5 - 24 Hr) from the moment the timer is set. The minimum resolution is 30 minutes.
CONTROL SYSTEM 12.11 Forced Operation Forced operation allows units to start, stop and operate in Cooling or Heating in pre-set temperature according to the following table: Pre-set Temp for : Forced operation mode WMF, WMN, WNG models Cooling 22°C Heating 28°C Note: •...
CONTROL SYSTEM 12.12 Sleep Mode Mode: Any Temp: Set – desired temperature selected Fan: Timer: Interact with Sleep Timer as described in sect 12.2 I Feel: On or Off The Sleep mode is activated by using the sleep button on the R/C. In Sleep Mode, the unit will automatically adjust the SPT to turn up/down the room temperature (RT) gradually to provide maximum comfort to the user in sleep.
Page 211
CONTROL SYSTEM 12.12.2 Time adjustment in Sleep Mode The user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below.
Page 212
CONTROL SYSTEM 12.13 Clogged Air Filter Filter LED ON after 512 HR. Filter LED is turned OFF, and the Filter Timer is restarted by pressing the reset button. 12-27 Service Manual - WNG Revision Y05-03 CONTENT...
Page 213
CONTROL SYSTEM 12.14 Controller Self-Test Procedure 12.14.1 By Shorting Test Jumper J1 SELF-TEST FLOW CHART FOR CONTROLLER (VERSION 4V5 OR HIGHER) SHORT JUMPER Step 1 RC/ST TEST (CONTROL PCB) MODEL CONFIGURATION TEST PRESS ON Step 2 POWER BUTTON STEP MOTOR TEST FREQUENCY TEST STANDBY...
Page 214
CONTROL SYSTEM 12.14.2 By Remote Control Settings: 1: TURNING ON THE POWER. Turn ON the power, make sure that the unit is in operation. STEP 2 : ENABLE SELF-TEST MODE • Use the remote control to send the first settings to display / indoor unit HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed.
Page 215
CONTROL SYSTEM STEP 4 : AUTO LED WALK TEST. • All the LEDS will turn OFF. • All the LEDS will turn ON for 1 second one by one in the following sequence: STAND-BY OPERATE TIMER FILTER COOL HEAT. • In PRX all the LEDS will turn ON for 1 second one by one in the following sequence : 18 °c 20 °c...
Page 216
CONTROL SYSTEM Fail condition: 0 sec - STAND-BY is turned ON 3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON • When the timing reset test is completed, the next test will start automatically. STEP 9: MEMORY TEST (EEPROM) •...
Page 217
CONTROL SYSTEM 12.15 On Unit Indicators and Controls Lights up when the Air Conditioner is connected to power and STAND BY ready to receive the R/C commands INDICATOR Blinks continuously in case of any thermistor failure. Lights up during operation. Blinks for 300 ms, to announce that a R/C infrared signal has been received and stored.
Page 218
CONTROL SYSTEM 12.16 Clock Random Delay From 0 to 2.5 seconds Clock Switch Open Clock Switch close The Clock is activate according to the following table: A/C STATE CLOCK STATE CLOCK ACTION A/C NEW STATE (clock is changed) (after clock is changed) before clock is changed) before clock is changed) OFF by...
Page 219
CONTROL SYSTEM 12.2 System Diagnostics Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LEDs. In diagnostic mode, system problems will be indicated by blinking of Heat & Cool LEDs. The coding method will be as follow: Heat led will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds.
Page 220
CONTROL SYSTEM 12.A CONTROL SYSTEM WNG 25/30/36 12A.1. Electronic Control 12A.1.1. Introduction The electronic control information is designed for service applications, and is common to the following groups of air-conditioners: • ST/ RC group - Cooling only / cooling and heating by heat pump. •...
Page 221
CONTROL SYSTEM 12A.2. Legend 12Α.2.1. Abbreviations - Alternate Current - Air-Conditioner - ON or OFF status CLOCK - ON/OFF Operation Input, (dry contact) COMP - Compressor - Central Processing Unit -Compensation Temperature Value ELUM - Extended Louver Upward Movement (Software Jumper) E²PROM, EEP - Erase Enable Programmable Read Only Memory - Heating Element...
Page 222
CONTROL SYSTEM 12A.3. Main PCB Controller 12Α.3.1. Display Board Display (LEXAN) Display PCB Ass’y FILTER LED OPR’ (STBY RED; ON: GREEN) OPR’ (STBY RED; ON: GREEN) RECIVER FILTER LED RECIVER FRESH, ION / ESF LCD SCREEN TIMER FRESH, ION / ESF LCD SCREEN TIMER 12a-3...
Page 223
CONTROL SYSTEM 12Α.3.2. List of A/C Models The model is divided by IFAN speed of PG motor. Model Type IFAN Speed Low : 900 rpm Medial : 1050 rpm WNG30 Wall Mounted High : 1300 rpm Strong : 1350 rpm Low : 750 rpm Medial : 900 rpm...
Page 224
CONTROL SYSTEM 12Α.3.3. List of A/C Groups The following table defines the different A/C groups, and the applicable operation modes for each group. Operating Mode Cool Heat Auto Cool/Heat Notes: 1. Electric heaters do the heating. 2. Heating is done by Compressor (Heat Pump), and by electric heaters. 12A.4.
Page 225
CONTROL SYSTEM 12Α.4.2. IFAN operation • Min time interval between IFAN speed changes in AUTOFAN Mode is 30 sec. • Max time interval between IFAN speed changes in H/M/L Mode is 60 sec. • Strong IFAN speed is only used in cool and heat mode and is controlled by R/C. Strong IFAN cannot be remembered by EEPROM.
Page 226
CONTROL SYSTEM 12Α.4.4. HE operation • Minimum Heaters ON or OFF time is 30 sec. • Heaters can never be in operation while IFAN is OFF. • In RH group, HE-1 will be activated only when COMP is not operating except in Dry Mode.
Page 227
CONTROL SYSTEM 12Α.1.7. RV Fault (comp units only) This test is performed every time the unit is switched from OFF/STBY to OPER in Heat mode or changes operation mode from COOL/DRY to HEAT (this applies also in AUTO COOL/HEAT mode). If ICT is lower than 35 C at the time of mode change, then at the first occurrence of 15 min continuous COMP operation, ICT is compared with ICT...
Page 228
CONTROL SYSTEM 12A.5. Cooling Mode 12Α.5.1. Cooling Mode – General • Room Temperature, RT, is detected by a) RAT in normal operation, or b) RCT (R/C sensor) in I-FEEL mode. • Indoor Coil Temp is detected by ICT (RT2). • Outdoor Coil Temp is detected by OCT (RT3).
Page 229
CONTROL SYSTEM 12Α.5.3. Sequence Diagrams • Maintaining room temp at desired level by comparing RT and SPT with user defined IFAN speed. (RT - SPT) [ COMP (WVL) OFAN USER FAN SPEED IFAN Note: 1) IFAN is always running at High, Medium, Low or Strong speed selected by user. 2) In IFEEL mode, the Room Temperature (RT) is the RCT from a R/C.
Page 230
CONTROL SYSTEM • Maintaining room temp at desired level by comparing RT and SPT with AUTO-IFAN. (RT - SPT) [ COMP (WVL) OFAN IFAN 12a-11 Service Manual - WNG Revision Y05-03 CONTENT...
Page 231
CONTROL SYSTEM 12A.6. Heating Mode 112Α.6.1. Heating Mode - General • Compensation Procedure: The compensation procedure comes to solve the problem of the temperature distribution by height during heat mode according to this procedure. • When I feel is OFF during heat mode: RT= RAT – CTV. When I feel is ON during heat mode: RT= RCT.
Page 232
CONTROL SYSTEM 12Α.6.2 IFAN operation rules for RC and SH. • As a general rule for RC and SH groups, IFAN will be switched ON according to the following graph: IFAN COMP ON Ducted General: Window: Note 1: When ICT is faulty: When the compressor switches from off to on (excluding deicing), IFAN will be on in ANY speed.
Page 233
CONTROL SYSTEM 12Α.6.3. Heaters operation rules for RC and SH groups • For both RC and SH groups, Heaters versus ΔT is as the following: T=SP-RT [ • Operation rules for Heaters in RC group: a. Heaters can be enabled only if IFAN is ON,.i.e IFAN is in higher precedence than the Heaters.
Page 234
CONTROL SYSTEM 12Α.6.4. OFAN Operation for RC and SH • As a general rule for RC and SH groups, excluding protection modes, OFAN starts with the compressor. • When OFAN is then ON it will operate according to the following conditions: a) OFAN operates together with the compressor.
Page 235
CONTROL SYSTEM 112Α.6.5. Heating, RC or SH Group Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: STRONG, HIGH, MED, LOW Timer: I Feel: On or Off Sequence Diagram Maintains room temp. at desired level by comparing RAT or RCT to SPT. (RT - SPT) [ COMP (WVL)
Page 236
CONTROL SYSTEM 12Α.6.6. Heating, RC or SH Group with Auto fan Mode: Heat, Auto (at heating) Temp: Selected desired temperature Fan: Auto Timer: I Feel: On or Off Sequence Diagram Maintains room temp at desired level by controlling COMP, IFAN and OFAN. (RT - SPT) [ COMP (WVL)
Page 237
CONTROL SYSTEM 12A.7. Automatic Cooling or Heating 12Α.7.1. Automatic Cooling or Heating - General • Mode Definition Mode: Auto Temp: Selected desired temperature Fan: Any (except STRONG) Timer: I Feel: On or Off • Switching-temperature between Cooling and Heating is SPT ± 3 •...
Page 238
CONTROL SYSTEM 12Α.7.2. Sequence Diagrams • Auto Cooling or Heating, RC or SH Groups Maintains room temp at desired level by selecting between cooling and heating modes. (RT - SPT) [ Auto Heat Mode Auto Cool Mode Auto Heat Mode >...
Page 239
CONTROL SYSTEM 12A.8. Dry Mode • Dry, ST or RC group with any group settings Mode: Dry Temp: Selected desired temp Fan: Timer: Any I FEEL: Control function Reduce room humidity with minimum temp ’fluctuations by operating in Cool Mode with low speed IFAN.
Page 240
CONTROL SYSTEM 12A.9. Protection • Cooling Mode Protections Indoor: Coil Defrost Mode: Cooling, Dry, Auto Temp: Selected desired temp. Fan: Timer: I Feel: On or Off Function: Protect the indoor coil from ice formation at low ambient temperature ICT [ OFAN COMP IFAN...
Page 241
CONTROL SYSTEM 12Α.9.1. High Pressure Protection Mode: (Auto) Cooling or Dry Temp: Selected desired temp. Fan: Timer: Any I Feel: On or Off Function: To protect the COMP from the high-pressure built-up in the outdoor coil during normal cooling operation, by changing the IFAN speed and switching OFF COMP. OCT [ COMP COMP is forced OFF...
Page 242
CONTROL SYSTEM 12Α.9.2. Heating Mode Protections • Outdoor coil Deicing (excluding RH Group) Mode: Heating, Auto (at heating) Temp: Selected desired Temp Fan: Timer: I FEEL: Function: Protects the Outdoor coil from ice formation by controlling COMP & RV operation. Scope This new deicer is designed to operate at extreme temp conditions.
Page 243
CONTROL SYSTEM • Deicing procedure OCT [ (DDT) 3 min 3 min max 12 min. COMP DI (note 1) DI (note 2) OFAN IFAN is forced to Low Speed IFAN HEs are forced ON IFAN Note 3 HEs are forced OFF OPER BLINK Notes:...
Page 244
CONTROL SYSTEM 12Α.9.3. High pressure protection (excluding RH Group) Mode: (Auto) Heating Fan: Timer: Any I Feel: On or Off Control Function Protect the Compressor from high pressure by switching OFF the OFAN and COMP. ICT [ COMP COMP is forced OFF OFAN is force OFAN OPER...
Page 245
CONTROL SYSTEM 12A.10. Timer Mode: Temp. Selected desired temp Fan: Timer: Timer On, Timer Off I Feel: On or Off Function: • Starts or stops the unit operation after pre-set time. If RC-1 is used, the timer setting will be (0.5 - 24 Hr) from the moment the timer is set.
Page 246
CONTROL SYSTEM 12A.11 Horizontal swing – Horizontal louvers • When the power is ON, the Horizontal Louver will reset to left of A/C (0˚) and then stop. • When the R/C signal of ON/OFF is received, the Horizontal louver will run to last position. •...
Page 247
CONTROL SYSTEM 12A.12. Forced operation Forced operation allows units to start, stop and operate in Cooling or Heating in pre- set temperature according to the following table: Forced operation mode Pre-set Temp Cooling 22°C Heating 28°C Note: • While under the forced operation, the temperature compensation schedule is disabled.
Page 248
CONTROL SYSTEM 12A.13. Sleep Mode: Temp: Set – desired temperature selected Fan: Timer: Interact with Sleep Timer as described in sect 12.2 I Feel: On or Off • The Sleep mode is activated by using the sleep button on the R/C. In Sleep Mode, the unit will automatically adjust the SPT to turn up/down the room temperature (RT) gradually to provide maximum comfort to the user in sleep.
Page 249
CONTROL SYSTEM 12Α.13.2. Time adjustment in Sleep Mode • In 10V4, the user can make use of the Off-Timer to extend the Sleep Time from 7 hours to 12 hour (max). The operation of the new “Extended Sleep Mode” is illustrated by the graphs below.
Page 250
CONTROL SYSTEM 12A.14. Clogged Air filter • Filter LED ON after 512 HR • Filter LED is turned OFF, and the Filter Timer is restarted by pressing the reset button. 12A.15. Ionizer Ionizer output logic Models: All Operation mode: All •...
Page 251
CONTROL SYSTEM 12A.17. Controller Self-Test Procedure 12Α.17.1. By Shorting Test Jumper J1 SELF-TEST FLOW CHART FOR CONTROLLER (VERSION 4V5 OR HIGHER) SHORT JUMPER Step 1 RC/ST TEST (CONTROL PCB) MODEL CONFIGURATION TEST PRESS ON Step 2 POWER BUTTON STEP MOTOR TEST FREQUENCY TEST STANDBY...
Page 252
CONTROL SYSTEM 12Α.17.2. By Remote Control Settings: 1: TURNING ON THE POWER. Turn ON the power, make sure that the unit is in operation. STEP 2 : ENABLE SELF-TEST MODE • Use the remote control to send the first settings to display / indoor unit HEAT mode, HIGH IFAN, set temperature to 16 ºC, no I-FEEL Sleep or any other timer settings are needed.
Page 253
CONTROL SYSTEM STEP 4 : AUTO LED WALK TEST. • All the LEDS will turn OFF. • All the LEDS will turn ON for 1 second one by one in the following sequence: STAND-BY OPERATE TIMER FILTER COOL HEAT. • In PRX all the LEDS will turn ON for 1 second one by one in the following sequence : 18 °c 20 °c...
Page 254
CONTROL SYSTEM Fail condition: 0 sec - STAND-BY is turned ON 3 sec - STAND-BY, OPER, TIMER and FILTER are turned ON • When the timing reset test is completed, the next test will start automatically. STEP 9: MEMORY TEST (EEPROM) •...
Page 255
CONTROL SYSTEM 12A.18. On Unit Indicators and Controls. STAND BY 1. Lights up when the Air Conditioner is connected to power INDICATOR and ready to receive the R/C commands 1. Lights up during operation. 2. Blinks continuously during OPERATION • OCT High Pressure Protection Mode INDICATOR •...
Page 256
CONTROL SYSTEM 12A.19. Clock Random Delay From 0 to 2.5 seconds Clock Switch Open Clock Switch close The Clock is activating according to the following table: A/C STATE CLOCK STATE CLOCK ACTION A/C NEW STATE (clock is changed) (after clock is changed) before clock is changed) before clock is changed) OFF by...
Page 257
CONTROL SYSTEM 12A.20. System diagnostics Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LEDs. In diagnostic mode, system problems will be indicated by blinking of Heat & Cool LEDs. The coding method will be as follow: Heat led will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds.
Page 258
CONTROL SYSTEM 12A.21. Quick Run Initiate the Quick Run Mode by using a R/C. Make sure that the correct A/C model has been selected by setting the jumpers J8, J3, J4 and J5 (if available), and the correct group has been selected by setting the jumpers J2 and J6.
Page 259
CONTROL SYSTEM 12B. CONTROL SYSTEM WNG 7-14 LCD TYPE 12B.1 General Functions 12B.1.1 Operation Modes • Auto Mode • Cooling Mode • Drying Mode • Fan Mode • Heating Mode 12B.1.2 Functions • I FEEL, • Forced Mode, • Protection - hot keep, Deicing, defrosting, •...
Page 260
CONTROL SYSTEM 12B.2 Main PCB Controller 12B.2.1 LCD Display WNG 7-14 Display (LEXAN) Display PCB Ass’y OPR’ (OFF: RED / ON: GREEN) FILTER LED OPR’ (OFF: RED / ON: GREEN) FILTER LED RECIVER RECIVER TIMER FRESH AIR /ION/ESF TIMER FRESH AIR /ION/ESF...
Page 261
CONTROL SYSTEM 12B.3 Operation Modes 12B.3.1 Auto Mode Operation Heating / Fan Drying Cooling 22ºC 26ºC • If RT >= 26ºC - A/C will go into Cooling Mode; Initial SPT is 25ºC. • If 22ºC < RT < 26ºC- A/C go into Drying mode; Initial SPT is 24ºC. •...
Page 262
CONTROL SYSTEM Comp’ Operation 12B.3.3 COMP SPT-1ºC SPT+1ºC • If RT >= SPT+1ºC, COMP and OFAN is activated; • If RT <= SPT-1ºC, COMP stop, OFAN will turn off after 5 seconds delay. Note: • COMP turns off have 3 min delay protection; •...
Page 263
CONTROL SYSTEM Defrosting 12B.3.4 ICT (ºC) >= 5 min 1 min >= 5 min COMP ON OFAN ON • IFAN always run at the set speed. • After COMP is on for 5 minutes, if (ICT <= -3ºC) during 1 minute, COMP and OFAN stop. If (ICT >...
Page 264
CONTROL SYSTEM 12B.3.5 High Pressure Protection (Excluding cooling only unit type) OCT (ºC) >= 3 min COMP Any OFAN follows COMP OFAN FORCED ON OFAN Any IFAN Any • If (OCT >= 61ºC), IFAN is forced to LOW. If (OCT <= 55ºC), IFAN restore to normal. •...
Page 265
CONTROL SYSTEM 12B.3.7 Drying Mode • SPT range: 16ºC~30ºC. Initial: 24ºC; • IFAN speed range: Auto, Low, Mid and Hi. Initial speed: Low; • IFAN speed can be changed only in state (1); State SPT-1°C SPT+2° SPT+3°C • If in state (1) - (SPT - 1ºC < RT <= SPT + 2ºC), unit will go into state (2) •...
Page 266
CONTROL SYSTEM 12B.3.8 Heating Mode • SPT range: 16ºC~30ºC. Initial: 24ºC; • In wall mounted units the indoor RT compensation temp’ value is - 3ºC -> RT, (Excluding I FEEL Mode) • IFAN speed range: Auto, Low, Mid and Hi. Initial speed: Low; •...
Page 267
CONTROL SYSTEM 12B.3.10 Hot keep function COMP on, IFAN set speed Supper low 21ºC 23ºC 32ºC 38ºC Note: If COMP is on for a period of 4 minutes or (ICT >= 38ºC), IFAN is in set speed; COMP off, IFAN set speed Supper low 21ºC...
Page 268
CONTROL SYSTEM 12B.3.12 High Pressure Protection ICT (ºC) >= 10s >= 3 Min COMP Any OFAN Any • If ICT >= 61ºC, OFAN turn off. If ICT <= 55ºC, OFAN turn on. • If (ICT >= 66ºC) for duration of 10 seconds, COMP turn off. If ICT <= 52ºC, COMP turn on. Note: If ICT is invalid, High Pressure protection cannot be activated.
Page 269
CONTROL SYSTEM 12B.3.14 Deicing Deicing starts, if OCT <= -6ºC and meets with one of the following conditions: • ICT < 39ºC, and IFAN is on for 20 minutes, and COMP is on for 5 minutes, and that ICT decrease 1ºC per 6 minutes, occur 3 times; •...
Page 270
CONTROL SYSTEM 12B.4 Other Functions 12B.4.1 Sleep Function Cooling or drying Mode SPT + 2ºC SPT + 1ºC Standby Heating Mode SPT - 2ºC SPT - 3ºC 1 hour 1 hour 6 hours • After 8 hours, it will go into Standby. Note: •...
Page 271
CONTROL SYSTEM 12B.4.3 I FEEL • The switchover between RCT by the remote controller and RT detected by the control board can be done by “I FEEL” function. After receiving the “I FEEL” command from the remote controller, MCU decide the operation mode of the air-conditioner by RCT detected by the remote controller.
Page 272
CONTROL SYSTEM 12B.4.7 Louvers control • Louvers is effective only if IFAN operates, but the remote controller can control its “ON” and “OFF” at any time after start up. When the air-conditioner is energized initially, the louvers is off, the following two modes can be controlled: (1) swing continuously; (2) cease any position in the swing range.
Page 273
CONTROL SYSTEM 12B.4.10 Sound Indication • The buzzer will beep twice when starts and a long sound when stops, one sound for receiving a command. 12B.4.11 Emergency Function • The first press on the emergency key on the indoor control board, the unit enters to cooling mode (SPT: 22ºC;...
Page 274
CONTROL SYSTEM 12B.4.15 Protection • When all relays meet their function requirements at the same time, there should be an interval of 0.5 second between every two relays. The action procedures are as follows: ON state: AHEAT OFAN —> COMP OFF state: AHEAT OFAN...
Page 275
CONTROL SYSTEM Self-test 12B.4.19 • When shorting the TEST jumper, the action will be per 1 second according to following: • beep one -> Cool led on-> Cool led off, Heat led on-> Heat led off, power led on-> power led off ,running led on->...
TROUBLESHOOTING TROUBLESHOOTING SYMPTON PROBABLE CAUSE CORRECTIVE ACTION The stand-by There is no correct voltage -If the voltage is low repair power indicator (red led) between the line and neutral supply. on the central terminals on main P.C.B control display -If there is no voltage repair panel doesn’t light general wiring.
Page 277
TROUBLESHOOTING SYMPTON PROBABLE CAUSE CORRECTIVE ACTION No cooling or Outdoor fan motor faulty or -Replace P.C.B. heating only other fault caused, compressor -Outdoor fan blocked remove indoor fan works. overload protection cut out. obstructions. Only indoor fan Outdoor fan blocked. -Remove obstructions.
EXPLODED VIEWS AND SPARE PARTS LISTS EXPLODED VIEWS AND SPARE PARTS LISTS 14.1 R410A 14.1.1 Indoor Unit NWNG 7,9,12,14 LCD NEW DESIGN Service Manual - WNG Revision Y05-03 14-1 CONTENT...
Page 279
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.2 Indoor Unit WNG 7 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526942 Grille C 26-Feb-04 Active 4527025 LCD Display Assy 26-Feb-04 Active 4518655 Air filter 26-Feb-04 Active 4519132...
Page 280
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.3 Indoor Unit WNG 9 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526942 Grille C 26-Feb-04 Active 4527025 LCD Display Assy 26-Feb-04 Active 4518655 Air filter 26-Feb-04 Active 4519132 ACTIVE CARBON FILTER ASSY 21-Sep-04 Active...
Page 281
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.4 Indoor Unit WNG 12 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526940 Grille A 24-Feb-04 Active 4527025 LCD LCD Display Assy 24-Feb-04 Active 4518655 Air filter 24-Feb-04 Active 4519132 ACTIVE CARBON FILTER ASSY 24-Feb-04...
Page 282
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.5 Indoor Unit WNG 14 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526942 Grille C 26-Feb-04 Active 4527025 LCD Display Assy 26-Feb-04 Active 4518655 Air filter 26-Feb-04 Active 4519132 ACTIVE CARBON FILTER ASSY 21-Sep-04 Active...
Page 283
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.6 Indoor Unit WNG 18, 21, 24 LCD 14-6 Revision Y05-03 Service Manual - WNG CONTENT...
Page 285
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.8 Indoor Unit WNG 21 LCD Item Code Item Desc 433133 IONIZER DISPLAY 906-191-07 433134 IONIZER POWER 906-191-01 4518113 AIR FILTER ASSY 4518651 Cover Side Motor 4518657 TUBE LOCK 4518662 Bearing assy fan 4518664 Drain hose 4521197 remote controller RC3...
Page 286
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.5 Indoor Unit WNG 18, 21, 24 LED Service Manual - WNG Revision Y05-03 14-9 CONTENT...
Page 287
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.10 Indoor Unit WNG 18, 24 LED Part No. Description Quantity 452917400 Grill A/WNG18 452952800 Grill B/WNG18 452952900 Grill C/WNG18 453024600 LED Display Assy. 452919800 Filter 4518113 Fiber Filter Assy. (Optional) 453054000 Frame assy./WNG18 4527144 Display Cover Assy 452919600...
Page 288
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.11 Indoor Unit WNG 21 LED Item Code Item Desc 433133 IONIZER DISPLAY 906-191-07 433134 IONIZER POWER 906-191-01 4518113 AIR FILTER ASSY 4518651 Cover Side Motor 4518657 TUBE LOCK 4518662 Bearing assy fan 4518664 Drain hose 4524963 Electrostatic Filter...
Page 289
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.12 Indoor Unit WNG 25,30, 36 LCD 14-12 Revision Y05-03 Service Manual - WNG CONTENT...
Page 290
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.13 Indoor Unit WNG 25 LCD Drawing Effective Item Code Item Desc Quantity Number Effective From 4525902 WNG-30 Grill ASSY. 14-Apr-04 Active 4523299 FILTER 14-Apr-04 Active 4523303 SHAFT LOCKER 14-Apr-04 Active 4518113 AIR FILTER ASSY 14-Apr-04 Active 4525610...
Page 291
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.14 Indoor Unit WNG 30 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4525902 WNG-30 Grill ASSY. 03-Mar-04 Active 4523299 FILTER 03-Mar-04 Active 4523303 SHAFT LOCKER 03-Mar-04 Active 4518113 AIR FILTER ASSY 03-Mar-04 Active 4525610...
Page 292
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.15 Indoor Unit WNG 36 LCD Item Code Item Desc 433133 IONIZER DISPLAY 906-191-07 433134 IONIZER POWER 906-191-01 438082 Thermistor Indoor 4516204 BEARING ASSY. FAN 4516263 SENSOR BASE 4518113 AIR FILTER ASSY 4518664 Drain hose 4519813 Thermistor room 4519815...
Page 293
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.16 Outdoor Unit ONG 7, 9, 12 ST 14-16 Revision Y05-03 Service Manual - WNG CONTENT...
Page 294
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.17 Outdoor Unit ONG 7 ST Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate 05-Mar-04 Active 4519251 Axial Fan OD=400 05-Mar-04...
Page 295
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.18 Outdoor Unit ONG 9 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 296
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.19 Outdoor Unit ONG 12 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 15-Nov-03 13-Jan-04 433219 Front Panel A1 13-Jan-04 Active 433221 Air Inlet Ring-420 15-Nov-03 Active 433223 Painting Insulation Plate...
Page 297
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.20 Outdoor Unit ONG 14 ST 14-20 Revision Y05-03 Service Manual - WNG CONTENT...
Page 298
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.21 Outdoor Unit ONG 14 ST Drawing Effective Item Code Item Desc Quantity Number Effective From 433219 Front Panel A1 01-Mar-04 15-Mar-04 433218 Front Panel A 15-Mar-04 Active 433221 Air Inlet Ring-420 01-Mar-04 Active 433223 Painting Insulation Plate 01-Mar-04...
Page 299
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.22 Outdoor Unit ONG 7 RC 14-22 Revision Y05-03 Service Manual - WNG CONTENT...
Page 300
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.23 Outdoor Unit ONG 7 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 301
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.24 Outdoor Unit ONG 9,12 RC 14-24 Revision Y05-03 Service Manual - WNG CONTENT...
Page 302
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.25 Outdoor Unit ONG 9 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 303
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.26 Outdoor Unit ONG 12 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 05-Mar-04 Active 433219 Front Panel A1 05-Mar-04 05-Mar-04 433221 Air Inlet Ring-420 05-Mar-04 Active 433223 Painting Insulation Plate...
Page 304
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.27 Outdoor Unit ONG 14 RC Service Manual - WNG Revision Y05-03 14-27 CONTENT...
Page 305
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.28 Outdoor Unit ONG 14 RC Drawing Effective Item Code Item Desc Quantity Number Effective From 433219 Front Panel A1 23-Feb-04 15-Mar-04 433218 Front Panel A 15-Mar-04 Active 433221 Air Inlet Ring-420 23-Feb-04 Active 433223 Painting Insulation Plate 23-Feb-04...
Page 306
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.29 Outdoor Unit GC 18 ST Service Manual - WNG Revision Y05-03 14-29 CONTENT...
Page 307
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.30 Outdoor Unit GC 18 ST Part No. Description Quantity 4517144 FAN COVER PP+UV 452795700 PAINTED LEFT CABINET ASSY 452989200 Base welding plate assy. 4516786 PAINTED RIGHT CABINET ASSY 4516985 Partition Plate 455000506 Compressor Capacitor With Screw 45uF (CBB65) 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 204107...
Page 308
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.31 Outdoor Unit GC 18 RC Service Manual - WNG Revision Y05-03 14-31 CONTENT...
Page 309
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.32 Outdoor Unit GC 18 RC Part No. Description Quantity 4517144 COVER PP+UV 452795700 PAINTED LEFT CABINET ASSY 452989200 Base welding plate assy. 4516786 PAINTED RIGHT CABINET ASSY 4516985 Partition Plate 455000506 Compressor Capacitor With Screw 45uF (CBB65) 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 204107...
Page 310
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.33 Outdoor Unit GC 21 RC Service Manual - WNG Revision Y05-03 14-33 CONTENT...
Page 311
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.34 Outdoor Unit GC 21 RC Part No. Description Version Qty 4517144 FAN COVER PP+UV 452795700 PAINTED LEFT CABINET ASSY 452989200 Base welding plate assy. 4516786 PAINTED RIGHT CABINET ASSY 4516985 Partition Plate 455000507 Compressor Capacitor With Screw 50uF (CBB65) 455000104 Double patch Capacitor for fan motor 4uF (CBB61S)
Page 312
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.35 Outdoor Unit GC 21 ST Service Manual - WNG Revision Y05-03 14-35 CONTENT...
Page 313
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.36 Outdoor Unit GC 21 ST Part No. Description Version Qty 4517144 COVER PP+UV 452795700 PAINTED LEFT CABINET ASSY 452989200 Base welding plate assy. 4516786 PAINTED RIGHT CABINET ASSY 4516985 Partition Plate 455000507 Compressor Capacitor With Screw 50uF (CBB65) 455000104 Double patch Capacitor for fan motor 4uF (CBB61S) 204107...
Page 314
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.37 Outdoor Unit GC 24 ST Service Manual - WNG Revision Y05-03 14-37 CONTENT...
Page 315
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.38 Outdoor Unit GC 24 ST Drawing Effective Number Effective From Item Code Item Desc Quantity FAN COVER PP+UV 14-May-04 Active 4517144 PAINTED LEFT CABINET ASSY 14-May-04 Active 452795700 452881901 Base plate paint assy. 14-May-04 Active 4516786...
Page 316
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.39 Outdoor Unit GC 24 RC Service Manual - WNG Revision Y05-03 14-39 CONTENT...
Page 317
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.40 Outdoor Unit GC 24 RC Drawing Effective Item Code Item Desc Quantity Number Effective From 4517144 FAN COVER PP+UV 14-May-04 Active 452795700 PAINTED LEFT CABINET ASSY 14-May-04 Active 452881901 Base plate paint assy. 14-May-04 Active 4516786...
Page 318
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.41 Outdoor Unit OU7-24 RC 1PH Service Manual - WNG Revision Y05-03 14-41 CONTENT...
Page 319
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.43 Outdoor Unit OU7-24 RC 1PH SP No. Part No. Description 190443 HEATER CRANKCASE MITSUBISHI 402283 SUCTION ACCUMULATOR 3"x5/8" 402495 BOARD TPHN 5B 433280 SIDE PANEL OU7-24 R410A 433281 SIDE GUARD OU7-24 R410 433285 COIL OU7-24 HDR 433291 TUBING ASSY OU7 R410A...
Page 320
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.44 Outdoor Unit OU7-24 ST 1PH Service Manual - WNG Revision Y05-03 14-43 CONTENT...
Page 321
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.44 Outdoor Unit OU7-24 ST 1PH SP No. Part No. Description 190443 HEATER CRANKCASE MITSUBISHI CO 402283 SUCTION ACCUMULATOR 3"x5/8" 3. 402495 BOARD TPHN 5B 433280 SIDE PANEL OU7-24 R410A 433281 SIDE GUARD OU7-24 R410 433293 COMPRESSOR NN27VBAMT 433705...
Page 322
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.45 Outdoor Unit OU7-24 RC 3PH Service Manual - WNG Revision Y05-03 14-45 CONTENT...
Page 323
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.46 Outdoor Unit OU7-24 RC 3PH SP No. Part No. Description 190443 HEATER CRANKCASE MITSUBISHI CO 402283 SUCTION ACCUMULATOR 3"x5/8" 3. 402494 BOARD TPHN 3C 433280 SIDE PANEL OU7-24 R410A 433281 SIDE GUARD OU7-24 R410 433285 COIL OU7-24 HDR 433291...
Page 324
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.47 Outdoor Unit OU7-24 ST 31PH Service Manual - WNG Revision Y05-03 14-47 CONTENT...
Page 325
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.48 Outdoor Unit OU7-24 ST 3PH SP No. Part No. Description 190443 HEATER CRANKCASE MITSUBISHI CO 402283 SUCTION ACCUMULATOR 3"x5/8" 3. 402494 BOARD TPHN 3C 433280 SIDE PANEL OU7-24 R410A 433281 SIDE GUARD OU7-24 R410 433705 NEW BASE ASSY OU 2005 LOCAL R4 433753...
Page 326
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.49 Outdoor Unit OU8-30 RC 1PH Service Manual - WNG Revision Y05-03 14-49 CONTENT...
Page 327
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.50 Outdoor Unit OU8-30 RC 1PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 402930 SIDE PANEL OU8-33 436357 SMALL ELECTRICAL COVER OU 439929 FRONT PANEL/COLLECTOR OU8-30 437091 OU SQUARE FAN GUARD 433294 NEW BASE ASSY OU 2005 EXPORT 433807...
Page 328
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.51 Outdoor Unit OU8-30 ST 1PH Service Manual - WNG Revision Y05-03 14-51 CONTENT...
Page 329
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.52 Outdoor Unit OU8-30 ST 1PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 402930 SIDE PANEL OU8-33 436357 SMALL ELECTRICAL COVER OU 439929 FRONT PANEL/COLLECTOR OU8-30 437091 OU SQUARE FAN GUARD 433705 NEW BASE ASSY OU 2005 LOCAL 433834...
Page 330
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.53 Outdoor Unit OU8-30 RC 3PH Service Manual - WNG Revision Y05-03 14-53 CONTENT...
Page 331
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.54 Outdoor Unit OU8-30 RC 3PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 402930 SIDE PANEL OU8-33 436357 SMALL ELECTRICAL COVER OU 439929 FRONT PANEL/COLLECTOR OU8-30 437091 OU SQUARE FAN GUARD 433294 NEW BASE ASSY OU 2005 EXPORT 433807...
Page 332
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.55 Outdoor Unit OU8-30 ST 3PH Service Manual - WNG Revision Y05-03 14-55 CONTENT...
Page 333
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.56 Outdoor Unit OU8-30 ST 3PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 402930 SIDE PANEL OU8-33 436357 SMALL ELECTRICAL COVER OU 439929 FRONT PANEL/COLLECTOR OU8-30 437091 OU SQUARE FAN GUARD 433705 NEW BASE ASSY OU 2005 LOCAL 433834...
Page 334
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.57 Outdoor Unit OU10-36 RC 1PH Service Manual - WNG Revision Y05-03 14-57 CONTENT...
Page 335
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.58 Outdoor Unit OU10-36 RC 1PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 439655 SIDE PANEL OU10 436357 SMALL ELECTRICAL COVER OU 439653 FRONT PANEL OU10 439662 GRILLE OU10 433294 NEW BASE ASSY OU 2005 EXPORT 433854...
Page 336
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.59 Outdoor Unit OU10-36 ST 1PH Service Manual - WNG Revision Y05-03 14-59 CONTENT...
Page 337
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.60 Outdoor Unit OU10-36 ST 1PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 439655 SIDE PANEL OU10 436357 SMALL ELECTRICAL COVER OU 439653 FRONT PANEL OU10 439662 GRILLE OU10 433705 NEW BASE ASSY OU 2005 LOCAL 433868...
Page 338
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.61 Outdoor Unit OU10-36 RC 3PH Service Manual - WNG Revision Y05-03 14-61 CONTENT...
Page 339
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.62 Outdoor Unit OU10-36 RC 3PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 439655 SIDE PANEL OU10 436357 SMALL ELECTRICAL COVER OU 439653 FRONT PANEL OU10 439662 GRILLE OU10 433294 NEW BASE ASSY OU 2005 EXPORT 433854...
Page 340
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.63 Outdoor Unit OU10-36 ST 3PH Service Manual - WNG Revision Y05-03 14-63 CONTENT...
Page 341
EXPLODED VIEWS AND SPARE PARTS LISTS 14.1.57 Outdoor Unit OU10-36 ST 3PH Drawing Number Item Code Item Description Quantity 437045 UPPER COVER EL13 OU LARGE 439655 SIDE PANEL OU10 436357 SMALL ELECTRICAL COVER OU 439653 FRONT PANEL OU10 439662 GRILLE OU10 433705 NEW BASE ASSY OU 2005 LOCAL 433868...
Page 342
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2 R407C 14.2.1 Indoor Unit WNG 7,9,12,14 LCD Service Manual - WNG Revision Y05-03 14-65 CONTENT...
Page 343
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.2 Indoor Unit WNG 7 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 09-Aug-02 Active 4518648 DISPLAY PANEL(White) 09-Aug-02 Active 4519419 WNG-1 Display basic assy 906-255-...
Page 344
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.3 Indoor Unit WNG 9 LCD Drawing Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132 ACTIVE CARBON FILTER ASSY 09-Aug-02...
Page 345
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.4 Indoor Unit WNG 12 LCD Drawing Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132 ACTIVE CARBON FILTER ASSY 09-Aug-02...
Page 346
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.5 Indoor Unit WNG 14 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132...
Page 347
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.6 Indoor Unit NWNG 7,9,12,14 LCD 14-70 Revision Y05-03 Service Manual - WNG CONTENT...
Page 348
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.7 Indoor Unit NWNG 7 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526944 Grille E 04-Mar-04 Active 4527025 LCD Display Assy 04-Mar-04 Active 4518655 Air filter 04-Mar-04 Active 4519132 ACTIVE CARBON FILTER ASSY 04-Mar-04 Active...
Page 349
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.8 Indoor Unit NWNG 9 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526944 Grille E 04-Mar-04 Active 4527025 LCD Display Assy 04-Mar-04 Active 4518655 Air filter 04-Mar-04 Active 4519132 ACTIVE CARBON FILTER ASSY 04-Mar-04 Active...
Page 350
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.9 Indoor Unit NWNG 12 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526944 Grille E 04-Mar-04 Active 4527025 LCD Display Assy 04-Mar-04 Active 4518655 Air filter 04-Mar-04 Active 4519132 ACTIVE CARBON FILTER ASSY 04-Mar-04 Active...
Page 351
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.10 Indoor Unit NWNG 14 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4526940 Grille A 02-Mar-04 Active 4527025 LCD Display Assy 02-Mar-04 Active 4518655 Air filter 02-Mar-04 Active 4519132 ACTIVE CARBON FILTER ASSY 02-Mar-04 Active...
Page 352
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.11 Indoor Unit WNG 7,9,12,14 LED Service Manual - WNG Revision Y05-03 14-75 CONTENT...
Page 353
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.12 Indoor Unit WNG 7 LED Drawing Item Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 09-Aug-02 Active 4518648 DISPLAY PANEL(White) 09-Aug-02 Active 4519419 WNG-1 Display basic assy 906-255-...
Page 354
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.13 Indoor Unit WNG 9 LED Drawing Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 28-Mar-03 Active 4518648 DISPLAY PANEL(White) 28-Mar-03 Active 4519419 WNG-1 Display basic assy 906-255- 28-Mar-03 Active 4519536 DISPLAY COVER (WHITH WITHOUT FREASH AIR) 28-Mar-03...
Page 355
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.14 Indoor Unit WNG 12 LED Item Drawing Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 28-Mar-03 Active 4518648 DISPLAY PANEL(White) 28-Mar-03 Active 4519419 WNG-1 Display basic assy 906-255- 28-Mar-03 Active 4519536 DISPLAY COVER (WHITH WITHOUT FREASH AIR)
Page 356
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.15 Indoor Unit WNG 14 LED Drawing Item Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 28-Mar-03 Active 4518648 DISPLAY PANEL(White) 28-Mar-03 Active 4519419 WNG-1 Display basic assy 906-255- 28-Mar-03 Active DISPLAY COVER (WHITH...
Page 357
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.16 Indoor Unit WNG 30 LCD 14-80 Revision Y05-03 Service Manual - WNG CONTENT...
Page 358
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.17 Indoor Unit WNG 30 LCD Drawing Effective Code Item Desc Quantity Number Effective From 4525648 WNG-30 PRINTING Grill ASSY Elco 02-May-03 24-Sep-03 4525902 WNG-30 Grill ASSY. 24-Sep-03 Active 4523299 FILTER 02-May-03 Active 4523303 SHAFT LOCKER 02-May-03 Active...
Page 359
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.18 Outdoor Unit GCN 7 RC 14-82 Revision Y05-03 Service Manual - WNG CONTENT...
Page 360
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.19 Outdoor Unit GCN 7 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 09-Aug-02 Active 4522552 Front panel A 09-Aug-02 17-Aug-04 4522551 Grille A of GCN 17-Aug-04 Active 436358...
Page 361
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.20 Outdoor Unit GCN 7 ST 14-84 Revision Y05-03 Service Manual - WNG CONTENT...
Page 362
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.21 Outdoor Unit GCN 7 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 09-Aug-02 Active 4522552 Front panel A 09-Aug-02 17-Aug-04 4522551 Grille A of GCN 17-Aug-04 Active 436358...
Page 363
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.222 Outdoor Unit ONG3 9,12 RC 14-86 Revision Y05-03 Service Manual - WNG CONTENT...
Page 364
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.23 Outdoor Unit ONG3 9 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 13-Jun-03 Active 433221 Air Inlet Ring-420 13-Jun-03 Active 433223 Painting Insulation Plate 13-Jun-03 Active 4519251 Axial Fan OD=400...
Page 365
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.24 Outdoor Unit ONG3 12 RC Item Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 13-Jun-03 Active 433221 Air Inlet Ring-420 13-Jun-03 Active 433223 Painting Insulation Plate 13-Jun-03 Active 4519251 Axial Fan OD=400...
Page 366
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.25 Outdoor Unit ONG3 9,12 ST Service Manual - WNG Revision Y05-03 14-89 CONTENT...
Page 367
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.26 Outdoor Unit ONG3 9 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 13-Jun-03 Active 433221 Air Inlet Ring-420 13-Jun-03 Active 433223 Painting Insulation Plate 13-Jun-03 Active 4519251 Axial Fan OD=400...
Page 368
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.27 Outdoor Unit ONG3 12 ST Item Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 13-Jun-03 Active 433221 Air Inlet Ring-420 13-Jun-03 Active 433223 Painting Insulation Plate 13-Jun-03 Active 4519251 Axial Fan OD=400...
Page 369
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.28 Outdoor Unit ONG3 14,18 RC 14-92 Revision Y05-03 Service Manual - WNG CONTENT...
Page 370
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.29 Outdoor Unit ONG3 14 RC Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 13-Jun-03 Active 433221 Air Inlet Ring-420 13-Jun-03 Active 433223 Painting Insulation Plate 13-Jun-03 Active 4519251 Axial Fan OD=400 13-Jun-03...
Page 371
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.30 Outdoor Unit ONG3 14,18 ST 14-94 Revision Y05-03 Service Manual - WNG CONTENT...
Page 372
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.31 Outdoor Unit ONG3-14 ST Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 13-Jun-03 Active 433221 Air Inlet Ring-420 13-Jun-03 Active 433223 Painting Insulation Plate 13-Jun-03 Active 4519251 Axial Fan OD=400 13-Jun-03 Active...
Page 373
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.32 Outdoor Unit OU8-30 3PH 14-96 Revision Y05-03 Service Manual - WNG CONTENT...
Page 374
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.33 Outdoor Unit OU8-30 3PH (page 2) Service Manual - WNG Revision Y05-03 14-97 CONTENT...
Page 375
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.34 Outdoor Unit OU8-30 3PH (page 3) 14-98 Revision Y05-03 Service Manual - WNG CONTENT...
Page 376
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.35 Outdoor Unit OU8-30 3PH Drawing Effective Code Item Desc Quantity Number Effective From 437045 LARGE UPPER COVER CUE 16-Dec-02 Active 402930 SIDE PANEL OU8-33 16-Dec-02 Active 436357 SMALL ELECTRICAL COVER CUE 16-Dec-02 Active 402928 FRONT PANEL OU8-33 EL13 16-Dec-02...
Page 377
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.36 Outdoor Unit OU8-33 ST/RC 1PH 14-100 Revision Y05-03 Service Manual - WNG CONTENT...
Page 378
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.37 Outdoor Unit OU8-33 ST/RC 1PH Service Manual - WNG Revision Y05-03 14-101 CONTENT...
Page 379
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.38 Outdoor Unit OU8-33 ST 1PH Item Drawing Code Item Desc Quantity Number Effective From Effective To 437045 LARGE UPPER COVER CUE 01-May-02 Active 436357 SMALL ELECTRICAL COVER CUE 18-May-03 Active 402928 FRONT PANEL OU8-33 EL13 01-May-02 Active 437091 OU SQUARE FAN GUARD...
Page 380
EXPLODED VIEWS AND SPARE PARTS LISTS 14.2.39 Outdoor Unit OU8-33 RC 1PH Item Drawing Code Item Desc Quantity Number Effective From Effective To 437045 LARGE UPPER COVER CUE 16-Dec-02 Active 402930 SIDE PANEL OU8-33 16-Dec-02 Active 436357 SMALL ELECTRICAL COVER CUE 18-May-03 Active 402928 FRONT PANEL OU8-33 EL13...
Page 381
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3 14.3.1 Indoor Unit WNG 7,9,12,14 LCD 14-104 Revision Y05-03 Service Manual - WNG CONTENT...
Page 382
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.2 Indoor Unit WNG 9 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132...
Page 383
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.3 Indoor Unit WNG 12 LCD Drawing Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132 ACTIVE CARBON FILTER ASSY...
Page 384
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.4 Indoor Unit WNG 14 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132...
Page 385
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.5 Indoor Unit WNG 7,9,12,14 LED 14-108 Revision Y05-03 Service Manual - WNG CONTENT...
Page 386
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.6 Indoor Unit WNG 7 LED Drawing Item Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 09-Aug-02 Active 4518648 DISPLAY PANEL(White) 09-Aug-02 Active 4519419 WNG-1 Display basic assy 906-255-...
Page 387
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.7 Indoor Unit WNG 9 LED Drawing Code Item Desc Quantity Number Effective From Effective To 4518647 WNG Grill A 09-Aug-02 Active 4518648 DISPLAY PANEL(White) 09-Aug-02 Active 4519419 WNG-1 Display basic assy 906-255- 09-Aug-02 02-Dec-03 4519416 DISPLAY COVER (WHITH WITH FREASH AIR)
Page 388
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.8 Indoor Unit WNG 12 LCD Drawing Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132 ACTIVE CARBON FILTER ASSY...
Page 389
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.9 Indoor Unit WNG 14 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4519364 WNG Grill B 09-Aug-02 Active 4521241 (Hua Lian) WNG LCD DISPLAY 09-Aug-02 Active 4518655 Air filter 09-Aug-02 Active 4519132...
Page 390
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.10 Indoor Unit WNG 25, 30 LCD Service Manual - WNG Revision Y05-03 14-113 CONTENT...
Page 391
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.11 Indoor Unit WNG 25 LCD Drawing Code Item Desc Quantity Number Effective From Effective To 4525902 WNG-30 Grill ASSY. 07-Aug-04 Active 4523299 FILTER 07-Aug-04 Active 4523303 SHAFT LOCKER 07-Aug-04 Active 4518113 AIR FILTER ASSY 07-Aug-04 Active 4525610...
Page 392
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.12 Indoor Unit WNG 30 LCD Drawing Item Code Item Desc Quantity Number Effective From Effective To 4525648 WNG-30 PRINTING Grill ASSY Elco 02-May-03 24-Sep-03 4525902 WNG-30 Grill ASSY. 24-Sep-03 Active 452836600 Controller/WNG 30 DST-8 916-255-32 02-Apr-04 Active 4523299...
Page 393
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.13 Outdoor Unit GCN 7,9,12 RC 14-116 Revision Y05-03 Service Manual - WNG CONTENT...
Page 394
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.14 Outdoor Unit GCN 7 RC Drawing Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 10-May-03 Active 4522551 Grille A of GCN 10-May-03 Active 436358 L. lifter 10-May-03 Active 4523441 Front panel A Painting assy...
Page 395
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.15 Outdoor Unit GCN 9 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 10-May-03 Active 4522551 Grille A of GCN 10-May-03 Active 436358 L. lifter 10-May-03 Active 4523441...
Page 396
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.16 Outdoor Unit GCN 12 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 10-May-03 Active 4522551 Grille A of GCN 10-May-03 Active 436358 L. lifter 10-May-03 Active 4523441...
Page 397
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.17 Outdoor Unit GCN 7,9,12 ST 14-120 Revision Y05-03 Service Manual - WNG CONTENT...
Page 398
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.18 Outdoor Unit GCN 12 ST Drawing Item Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 10-May-03 Active 4522551 Grille A of GCN 10-May-03 Active 436358 L. lifter 10-May-03 Active 4523441...
Page 399
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.19 Outdoor Unit ONG3 9,12 RC 14-122 Revision Y05-03 Service Manual - WNG CONTENT...
Page 400
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.20 Outdoor Unit ONG 9 RC Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 09-Aug-02 Active 433223 Painting Insulation Plate 09-Aug-02 Active 4519251 Axial Fan OD=400 09-Aug-02 Active 4519250 Fan Motor YDK30-6V 09-Aug-02...
Page 401
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.21 Outdoor Unit ONG3 12 RC Drawing Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 09-Aug-02 Active 433221 Air Inlet Ring-420 09-Aug-02 Active 433223 Painting Insulation Plate 09-Aug-02 Active 4519251 Axial Fan OD=400 09-Aug-02...
Page 402
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.22 Outdoor Unit ONG3 14,18, RC Service Manual - WNG Revision Y05-03 14-125 CONTENT...
Page 403
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.23 Outdoor Unit ONG3 14 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 433218 Front Panel A 09-Aug-02 Active 433221 Air Inlet Ring-420 09-Aug-02 Active 433223 Painting Insulation Plate 09-Aug-02 Active 4519251 Axial Fan OD=400...
Page 404
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.24 Outdoor Unit GC 14 RC Service Manual - WNG Revision Y05-03 14-127 CONTENT...
Page 405
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.25 Outdoor Unit GC 14 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 09-Aug-02 Active 372332 Fan cover 09-Aug-02 Active 436358 L. lifter 09-Aug-02 Active 4516159 Front panel Painting assy 09-Aug-02...
Page 406
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.26 Outdoor Unit GC 14 ST Service Manual - WNG Revision Y05-03 14-129 CONTENT...
Page 407
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.27 Outdoor Unit GC 14 ST Drawing Code Item Desc Quantity Number Effective From Effective To 4516158 Cover panel Painting assy 09-Aug-02 Active 372332 Fan cover 09-Aug-02 Active 436358 L. lifter 09-Aug-02 Active 4516159 Front panel Painting assy 09-Aug-02 Active...
Page 408
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.28 Outdoor Unit GC 18, 24 RC Service Manual - WNG Revision Y05-03 14-131 CONTENT...
Page 409
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.29 Outdoor Unit GC 24 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 4517144 FAN COVER PP+UV 09-Aug-02 Active 4517029 PAINTED LEFT CABINET ASSY 09-Aug-02 Active 4517612 BASE PAN ASSY 09-Aug-02 04-Dec-03 4526273...
Page 410
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.30 Outdoor Unit GC 18, 24 ST Service Manual - WNG Revision Y05-03 14-133 CONTENT...
Page 411
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.31 Outdoor Unit GC 24 ST Drawing Code Item Desc Quantity Number Effective From Effective To 4517144 FAN COVER PP+UV 09-Aug-02 Active 4517029 PAINTED LEFT CABINET ASSY 09-Aug-02 Active 4517612 BASE PAN ASSY 09-Aug-02 12-Feb-04 4526273 BASE PAN PAINTED ASSY...
Page 412
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.32 Outdoor Unit GC 30 RC Service Manual - WNG Revision Y05-03 14-135 CONTENT...
Page 413
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.33 Outdoor Unit GC 30 RC Drawing Item Code Item Desc Quantity Number Effective From Effective To 4523657 PAINTED TOP COVER ASSY 07-Apr-03 Active 4522600 Left Handle 07-Apr-03 Active 4522604 outlet grid 07-Apr-03 Active 4523652 PAINTED LEFT CABINET ASSY 07-Apr-03...
Page 414
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.34 Outdoor Unit OU8-30 1PH RC Service Manual - WNG Revision Y05-03 14-137 CONTENT...
Page 415
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.35 Outdoor Unit OU8-30 RC 1PH ( page 2) 14-138 Revision Y05-03 Service Manual - WNG CONTENT...
Page 416
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.36 Outdoor Unit OU8-30 RC 1PH Drawing Code Item Desc Quantity Number Effective From Effective To 437045 LARGE UPPER COVER CUE 16-Jun-03 Active 436357 SMALL ELECTRICAL COVER CUE 16-Jun-03 Active 402928 FRONT PANEL OU8-33 EL13 16-Jun-03 Active 437091...
Page 417
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.37 Outdoor Unit OU8-30 RC 3PH 14-140 Revision Y05-03 Service Manual - WNG CONTENT...
Page 418
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.38 Outdoor Unit OU8-30 RC 3PH Service Manual - WNG Revision Y05-03 14-141 CONTENT...
Page 419
EXPLODED VIEWS AND SPARE PARTS LISTS 14.3.39 Outdoor Unit OU8-30 RC 3PH Drawing Effective Item Code Item Desc Quantity Number Effective From 437045 LARGE UPPER COVER CUE 16-Jun-03 Active 436357 SMALL ELECTRICAL COVER CUE 16-Jun-03 Active 402928 FRONT PANEL OU8-33 EL13 16-Jun-03 Active 437091...
OPTIONAL ACCESSORIES OPTIONAL ACCESSORIES 15.1 RCW Wall Mounted Remote Control 15.1.1 The RCW wall mounted remote control can be fitted to a large range and models, It can be used as IR (wirless mode) or wired controler. the RCW can control up to15 indoor units using the same settings (on its wired aplication), The max wiring length between the controller to the last indoor unit is 300m.
Page 421
OPTIONAL ACCESSORIES 15.2 RCW2 Wall Mounted Remote Cntrol 15.2.1 The RCW2 wall mounted remote controler is a wired controler that can provide affective controling management up to 15 different settings and temp’ zones. The RCW2 can be connected up to a max’ of 32 units,allowing a max wiring length of 1000m.
Page 422
OPTIONAL ACCESSORIES 15.3 RCW/RCW2 Wiring Connections as Shown on Kit 15-3 Service Manual - WNG Revision Y05-03 CONTENT...
Page 423
OPTIONAL ACCESSORIES 15.4 A.S.K (All Season Kit) The A.S.K is a pressure regulator to be installed on site in case the working conditions are below the standard operating range of the unit in cooling mode. The ASK allows working in cooling at low temp’ up to -10 ºC for rooms with high internal gains. For units up to 7.2 KW kit code no’...
Page 428
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► INSTALLATION AND OPERATION MANUAL WNG 7,9,12,14 LED ► INSTALLATION AND OPERATION MANUAL WNG 7,9,12,14 LCD ► INSTALLATION AND OPERATION MANUAL WNG 18, 21, 24 ► INSTALLATION AND OPERATION MANUAL WNG 25,30, 36...
Page 429
CLIMATIZADOR SPLIT MURAL ESPANOL AIR CONDITIONER SPLIT WALL MOUNTED ENGLISH CONDICIONADOR DE AR SPLIT -MONTADO NO CHAO PORTUGUES CONDIZIONATORE D'ARIA A PARETE SPLIT ITALIANO •• •• M A N U A L E D I U T I L I Z Z O E D I P R O G R A M M A Z I O N E P R O G R A M M I N G A N D O P E R A T I N G...
Page 430
AIR CONDITIONER SPLIT WALL MOUNTED PROGRAMMING AND OPERATING CONTENT...
Page 431
CONTENTS Introduction If your air conditioner is for cooling only,please System Description disregard the heating Modes of Operation, Functions and Features instructions Use of Wireless Remote Control Please read these instructions On-unit indicators and controls before operating the air Remote Control conditioner Operation procedure Turning on the Air Conditioner...
Page 432
INTRODUCTION The air conditioner is designed for various uses: Cooling in summer. OPERATING TEMPERATURE RANGE: Dehumidifying at high humidity conditions. (According to T temperature condition) Cooling: 43 C Heating. Heating: 21 C R22 21 C R407C & R410A Air Filtration Ventilation IMPORTANT NOTICE: The air conditioner must be...
SYSTEM DESCRIPTION 1.Air intake grille 2.Air filter 3.Supply air flap 4.Air outlet •• •• 5.Unit's indicators 6.Horizontal Air flow Deflecting louvers 7.On unit's controls 8.Power cord MO DE 9.Outdoor unit air intake 10.Power cable 11.control wire 12.Air-fresh controls wire (optional) 13.Liquid line 14.Suction line 15.Air-fresh hose (optional)
Page 434
MODES OF OPERATION, FUNCTIONS AND FEATURES COOL Cools, dehumidifies and filters the room air. Maintains desired room temperature. HEATING Heats and filters the room air. Maintains the desired room temperature. AUTO Automatically switches from COOLING to HEATING or from HEATING to COOLING, maintaining the desired temperature according to the room conditions.
Page 435
% RH HUMIDITY Measures and displayes relative humidity between 30% and 90% at a MEASURE temperature range of 15 c to 45 c. MENT (OPTIONAL) AUTO FLAP The air flap (louvers) is automatically positioned for the most suitable blow-out angle, when COOL, HEAT, DRY or FAN modes are selected. When the air conditioner is turned off, the flap will close automatically for an aesthetic appearance.
USE OF WIRELESS REMOTE CONTROL PRIOR TO OPERATION Prior to operating your air conditioner,make sure of the following procedures: •• •• Insert the plug of indoor unit to power supply properly. Indicator (A) on air conditioner lights on, indicating air conditioner is ready to receive signals from remote control.
Page 437
ON-UNIT INDICATORS AND CONTROLS A. Stand-by / Operation indicator Lights up in red when connected to power. Lights up in green during operation. B. Fresh-air / lonizer indicator Lights up when the fresh-air or lonizer operation. C. LCD operation display D.
REMOTE CONTROL START/STOP button Operation mode selection button COOLING HEATING AUTO COOL/HEAT I FEEL temperature sensing mode button FAN SPEED and AUTO FAN button Room temperature Up button AUTO Room temperature DOWN button SLEEP button Airflow direction AUTO-CONTROL MODE button HORIZONTAL Airflow direction F/AIR AUTO-CONTROL button...
OPERATION PROCEDURE TURNING ON THE AIR CONDITIONER Press START/STOP button (1) to turn on the air condi t ioner on. Indicator (A) on the air conditioner will light up,indicating that the unit is in operation.Note that the LCDoperation display (13) will always show the last mode of operation and previous function used.
Page 440
AUTO COOLING/HEATING OPERATION Select the AUTO mode by pressing MODE button (2). Switch to the desired FAN SPEED or to AUTO FAN by pressing button (4). Select suitable temperature setting. The air flap will automatically move to either horizontal air delivery for cooling or to vertical air delivery for heating. At start, the air conditioner will select its mode of operation according to the room temperature and the temperature setting.
Page 441
TIMER OPERATION Press TIMER select button (11) to activate the timed operation mode. Each time you press TIMER button (11), one of the following four operation modes will appear on the LCD disp lay. The operation modes are sequenced in turn in the direction of arrow. During Timer operation, the indicator on the air conditioner will light up.
Page 442
AIR DIRECTION OPERATION 1.Air Direction Positioning Press button (8) to position the air flap to any desired angle. 2.Automatic Vertical Air Swing Press button (9) to activate the auto air swing. Press button (8) to deactivate this function. TURNING OFF THE AIR CONDITIONER Press START/STOP button (1) to turn off the air conditioner.
Page 443
FRESH AIR FNCTION (optional) PRESS THE FRESH AIR button (17) to activate the Fresh air function and press the button again to cancel this function. IONIZER AND ELECTROSTATIC FILTER Press the IONIZER button (10) to activate the lonizer and Electrostatic Filter function , if the lonizer switch at ON position, the blue indicator on the lonizer lights up.
Page 444
PROTECTION MODES Your air-conditioner includes several auto protection modes which enables you to use it virtually at any time and in any season regardless of the outdoor temperature. Some of the protection modes are listed below: Mode Operation Protection Controlled remedy conditions from...
CARE AND MAINTENANCE Before performing any maintenance procedure, make sure to disconnect the air conditioner from the power. CLEANING THE AIR FILTER Your air conditioner is provided with a filter cleaning indicator. When the indicator (E)lights up, the filters should be removed for cleaning To remove the air filters, lift up the panel.
OPERATING TIPS Set a suitable room temperature; excessively low room temperature is not good for your health and wastes electricity. Avoid frequent setting of the temperature. During cooling, avoid direct sun. Keep curtains and blinds closed. Close doors and windows to keep the cool air in the room. Avoid generating heat or using of heating appliances while the air conditioner in cooling mode.
Page 447
PRECAUTIONS Use the proper electrical fuse.. Do not pull out the power cord unless the unit is turned off. Do not turn on or off air conditioner by inserting the power cord. Do not obstruct or block the air inlet or air outlet of the air conditioner.
BEFORE CALLING FOR SERVICE Before calling for service, please check the following common malfunctions and correct it as needed. Problem Cause Remedy Plug in the power Unit does not Unit not connected cord. operate. Stand- to power by indicator does Check main fuse.
INSTALLATION INSTRUCTIONS ENGLISH 1. ACCESSORIES SUPPLIED WITH AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNITS 3. ELECTRICAL REQUIREMENTS 4. INSTALLATION OF THE INDOOR UNIT 5. CONDENSATE HOSE CONNECTION 6. ELECTRICAL CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS 7. REFRIGERANT TUBING 8.
Page 450
I N S T A L L A T I O N I N S T R U C T I O N S FOR SPLIT WALL MOUNTED AIR CONDITIONER LOCATION OF INDOOR AND ACCESSORIES SUPPLIED WITH OUTDOOR UNITS THE AIR CONDITIONER Select the location considering the following: Shape Name...
Page 451
Fig.3 Length of electric cable to mains 950mm 1800mm •• • • 80 mm Fig 3 50 mm 50 mm •• •• 2300 mm Fig 4 Fig.5 1. To attach 2. To remove 100 mm 100 mm 500 mm 400 mm 100 mm Fig 5 Fig 6...
Page 452
ELECTRICAL REFRIGERATION TUBE ROUTING REQUIREMENTS 1. There are five possible routes for installing the refrigeration tube as shown. Electrical wiring and connections should be made by qualified 2. For route (6), cut the bottom notch in the rear. electricians and in accordance with local electrical codes and 3.
Page 453
PENETRATION OF WALL FOR TUBING CONDENSATE HOSE 1. Mark the location of the hole on either side of the mounting CONNECTION plate as shown. and drill it at a 5 downward angle, as shown. 1. Attach the condensate drain hose to the corrugated hose in the 2.
Page 454
ELECTRICAL CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS 1. To connect the indoor unit to the outdoor nit MULTIPLE WIRE POWER CABLE use the following electrical cables, protected for outdoor use: Cooling and heating model: Multiple wire cable (220-240V, 50Hz). 5 wires x 1.5 mm 5 wires x 0.5 mm - for low voltage Fig18 (supplied with the unit).
REFRIGERANT TUBING Tightening TUBE SIZE TORQUE torques of unions Liquid line 1/4" 15-20 N.M. and valve caps: Suction line 3/8" 30-35 N.M. CONNECT THE INDOOR TO THE OUTDOOR UNIT Suction line 1/2" 50-54 N.M. Suction line 5/8" 75-78 N.M. The indoor unit contains a small quantity of refrigerant. Do not unscrew the nuts from the unit until you are ready to connect the Fig.23 Fig.24...
Page 456
INSTALL THE AIR-FRESH HOSE (optional) A 5m of air-refreshing hose is supplied •• •• with this equipment. You can lengthen the hose with another hose supplied by the pro fessional installer in the installation if it is needed. Use the hose elbow and clamps to joint the smaller end ( 30) of the added hose with the original one, and then fix the other end with the interface of the propeller...
Page 457
FINAL TASKS 1. Replace all valve caps and ensure that they are tightened properly. 2. Fill gaps on the wall between hole sides and tubing with sealer. 3. Attach wiring and tubing to the wall with clamps where necessary. 4. Operate the air conditioner together with the customer and explain all functions. 5.
Page 458
AIR CONDITIONER SPLIT WALL MOUNTED PROGRAMMING AND OPERATING MANUAL I N S T A L L A T I O N I N S T R U C T I O N S CONTENT...
Page 459
CONTENTS Introduction If your air conditioner is for cooling only,please System Description disregard the heating Modes of Operation, Functions and Features instructions Use of Wireless Remote Control Please read these instructions On-unit indicators and controls before operating the air Remote Control conditioner Operation procedure Turning on the Air Conditioner...
Page 460
INTRODUCTION The air conditioner is designed for various uses: Cooling in summer. Dehumidifying at high humidity conditions. Heating. Air Filtration Ventilation IMPORTANT NOTICE: Tis air conditioner must be grounded to protect against electrical shock. Installation of the air conditioner must be performed by an experienced air conditioning installer, observing good refrigeration...
Page 461
SYSTEM DESCRIPTION 1.Air intake grille 2.Air filter 3.Supply air flap 4.Air outlet 5.Unit's indicators 6.Horizontal Air flow Deflecting lovers 7.On unit's controls 8.Power cord MO DE 9.Outdoor unit air intake 10.Power cable 11.control wire 12.Air-fresh controls wire (optional) 13.Liquid line 14.Suction line 15.Air-fresh hose (optional) 16.Drain hose...
Page 462
MODES OF OPERATION, FUNCTIONS AND FEATURES COOL Cools, dehumidifies and filters the room air. Maintains desired room temperature. HEATING Heats and filters the room air. Maintains the desired room temperature. AUTO Automatically switches from COOLING to HEATING or from HEATING to COOLING, maintaining the desired temperature according to the room conditions.
Page 463
% RH HUMIDITY Measures and displayes relative humidity between 30% and 90% at a MEASURE temperature range of 15 c to 45 c. MENT (OPTIONAL) AUTO FLAP The air flap (louvers) is automatically positioned for the most suitable blow-out angle, when COOL, HEAT, DRY or FAN modes are selected. When the air conditioner is turned off, the flap will close automatically for an aesthetic appearance.
Page 464
USE OF WIRELESS REMOTE CONTROL PRIOR TO OPERATION Prior to operating your air conditioner, make sure of the following procedures: Insert the plug of indoor unit to power supply properly. Indicator (C) on air conditioner lights on, indicating air conditioner is ready to receive signals from remote control.
Page 465
ON-UNIT INDICATORS AND CONTROLS CONTENT...
Page 466
REMOTE CONTROL START/STOP button Operation mode selection button COOLING HEATING AUTO COOL/HEAT I FEEL temperature sensing mode button FAN SPEED and AUTO FAN button Room temperature Up button AUTO Room temperature DOWN button SLEEP button Airflow direction AUTO-CONTROL MODE button HORIZONTAL Airflow direction F/AIR AUTO-CONTROL button...
Page 467
OPERATION PROCEDURE TURNING ON THE AIR CONDITIONER Press START/STOP button (1) to turn on the air conditioner on. Indicator (A) on the air conditioner will light up,indicating that the unit is in operation.Note that the LCDoperation display (13) will always show the last mode of operation and previous function used.
Page 468
AUTO COOLING/HEATING OPERATION Select the AUTO mode by pressing MODE button (2). Switch to the desired FAN SPEED or to AUTO FAN by pressing button (4). Select suitable temperature setting. The air flap will automatically move to either horizontal air delivery for cooling or to vertical air delivery for heating. At start, the air conditioner will select its mode of operation according to the room temperature and the temperature setting.
Page 469
TIMER OPERATION Press TIMER select button (11) to activate the timed operation mode. Each time you press TIMER button (11), one of the following four operation modes will appear on the LCD display. The operation modes are sequenced in turn in the direction of arrow. During Timer operation, the indicator on the air conditioner will light up.
Page 470
AIR DIRECTION OPERATION 1.Air Direction Positioning Press button (8) to position the air flap to any desired angle. 2.Automatic Vertial Air Swing Press button (9) to activate the auto air swing.Press button (8) to deactivate this function. TURNING OFF THE AIR CONDITIONER Pree START/STOP button (1) to turn off the air conditioner.Indicator (A) on the air cinditioner will be turned off.Indicator (G) will stay lit,indicating that the air cinditioner is in STAND-BY mode and ready to accept any new...
Page 471
FRESH AIR FNCTION (optional) PRESS THE FRESH AIR button (17) to activate the Fresh air function and press the button again to cancel this function. IONIZER AND ELECTROSTATIC FILTER Press the IONIZER button (10) to activate the lonizer and Electrostatic Filter function , if the lonizer switch at ON position, the blue indicator on the lonizer lights up.
Page 472
PROTECTION MODES Your air-conditioner includes several auto protection modes which enables you to use it virtually at any time and in any season regardless of the outdoor temperature. Some of the protec-tion modes are listed below: Mode Operation Protection Controlled remedy conditions from...
Page 473
CARE AND MAINTENANCE Before performing any maintenance procedure, make sure to disconnect the air conditioner from the power. CLEANING THE ELECTROSTATIC FILTER The electrostatic filter should be removed from the unit and cleaning once three month.The procedure is shown as following; 1 open the front panel 2 push the hook on the filter and pull out the electrostatic filter (Fig )
Page 475
PRECAUTIONS Use the proper electrical fuse.. Do not pull out the power cord unless the unit is turned off. Do not turn on or off air conditioner by inserting the power cord. Do not obstruct or block the air inlet or air outlet of the air conditioner.
Page 476
BEFORE CALLING FOR SERVICE Before calling for service, please check the following common malfunctions and correct it as needed. Problem Cause Remedy Unit does not operate. Stand- by indicator does not light up. Unit does not operate. Stand indicator lights. Unit does not respond properly to remote control...
Page 477
INSTALLATION INSTRUCTIONS ENGLISH 1. ACCESSORIES SUPPLIED WITH AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNITS 3. ELECTRICAL REQUIREMENTS 4. INSTALLATION OF THE INDOOR UNIT 5. CONDENSATE HOSE CONNECTION 6. ELECTRICAL CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS 7. REFRIGERANT TUBING 8.
Page 478
I N S T A L L A T I O N I N S T R U C T I O N S FOR SPLIT WALL MOUNTED AIR CONDITIONER LOCATION OF INDOOR AND ACCESSORIES SUPPLIED WITH OUTDOOR UNITS THE AIR CONDITIONER Select the location considering the following: INDOOR UNIT 1.
Page 479
Fig.3 Length of electric cable to mains 950mm 1800mm 80 mm Fig 3 50 mm 50 mm 2300 mm Fig 4 Fig.5 1. To attach 2. To remove 100 mm 100 mm OF F 500 mm 400 mm AU TO 100 mm Fig 5 Fig 6...
Page 480
ELECTRICAL REFRIGERATION TUBE ROUTING REQUIREMENTS 1. There are five possible routes for installing the refrigeration tube as shown. Electrical wiring and connections should be made by qualified 2. For route (6), cut the bottom notch in the rear. electricians and in accordance with local electrical codes and 3.
Page 481
PENETRATION OF WALL FOR TUBING CONDENSATE HOSE 1. Mark the location of the hole on either side of the mounting CONNECTION plate as shown. and drill it at a 5 downward angle, as shown. 1. Attach the condensate drain hose to the corrugated hose in the 2.
Page 482
ELECTRICAL CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS 1. To connect the indoor unit to the outdoor nit MULTIPLE WIRE POWER CABLE use the following electrical cables, protected for outdoor use: Cooling and heating model: Multiple wire cable (220-240V, 50Hz). 5 wires x 1.5 mm 5 wires x 0.5 mm - for low voltage Fig18 (supplied with the unit).
Page 483
REFRIGERANT TUBING Tightening TUBE SIZE TORQUE torques of unions Liquid line 1/4" 15-20 N.M. and valve caps: Suction line 3/8" 30-35 N.M. CONNECT THE INDOOR TO THE OUTDOOR UNIT Suction line 1/2" 50-54 N.M. Suction line 5/8" 75-78 N.M. The indoor unit contains a small quantity of refrigerant. Do not unscrew the nuts from the unit until you are ready to connect the Fig.23 Fig.24...
Page 484
INSTALL THE AIR-FRESH HOSE (optional) air pipe joint air fresh hose CONTENT...
Page 485
FINAL TASKS 1. Replace all valve caps and ensure that they are tightened properly. 2. Fill gaps on the wall between hole sides and tubing with sealer. 3. Attach wiring and tubing to the wall with clamps where necessary. 4. Operate the air conditioner together with the customer and explain all functions. 5.
Page 486
AIR CONDITIONER SPLIT WALL MOUNTED ENGLISH CONDITIONNEUR D 'AIR MONTE SUR PAROI EN DEUX UNITES FRANCAIS KLIMAGERAET IN SPLIT BAUWEISE DEUTSCH CLIMATIZADOR SPLIT MURAL ESPANOL CONDIZIONATORE D'ARIA A PARETE SPLIT ITALIANO •• •• P R O G R A M M I N G A N D O P E R A T I N G M A N U A L M A N U E L D E P R O G R A M M A T I O N E T D O P E R A T I O N B E D I E N U N G S U N D P R O G R A M M I E R U N G S H A N D B U C H M A N U A L D E U T I L I Z A C I O N Y D E P R O G R A M M A C I O N...
Page 488
CONTENTS Introduction If your air conditioner is for cooling only,please System Description disregard the heating Modes of Operation, Functions and Features instructions Use of Wireless Remote Control Please read these instructions On-unit indicators and controls before operating the air Remote Control conditioner Operation procedure Turning on the Air Conditioner...
Page 489
INTRODUCTION This Split Air Conditioner is designed for versatile applications: Cooling OPERATING TEMPERATURE RANGE: Dehumidifying at high humidity conditions. (According to T temperature condition) Cooling: 43 C Heating Heating: 21 C R407C & R410A 21 C Air Filtration Ventilation IMPORTANT NOTICE: The air conditioner must be grounded to protect against electrical shock.
Page 490
SYSTEM DESCRIPTION 1.Air intake grille 2.Air filter 3.Supply air flap 4.Air outlet •• •• 5.Unit's indicators 6.Horizontal Air flow Deflecting louvers 7.On unit's controls 8.Power cord 9.Outdoor unit air intake 10.Power cable 11.control wire 12.Air-fresh controls wire (optional) 13.Liquid line 14.Suction line 15.Air-fresh hose (optional) 16.Drain hose...
Page 491
MODES OF OPERATION, FUNCTIONS AND FEATURES COOL Cools, dehumidifies and filters the room air. Maintains desired room temperature. Heats and filters the room air. Maintains the desired room temperature. HEATING AUTO Automatically choose COOLING or HEATING or DRY , maintaining the desired temperature according to the room conditions. Dehumidifies and softly cools the room In DRY Mode, the air conditioner operates at an inceased dehumidifying power.
Page 492
AUTO FLAP The air flap (louvers) is automatically positioned for the most suitable blow-out angle, when COOL, HEAT, DRY or FAN modes are selected. When the air conditioner is turned off, the flap will close automatically for an aesthetic appearance. VERTICAL AIR Automatic swing of supply air in vertical direction.
Page 493
USE OF WIRELESS REMOTE CONTROL PRIOR TO OPERATION Prior to operating your air conditioner,make sure of the following procedures: •• •• Insert the plug of indoor unit to power supply properly. Indicator (A) on air conditioner lights on, indicating air conditioner is ready to receive signals from remote control.
Page 494
ON-UNIT INDICATORS AND CONTROLS A. Stand-by / Operation indicator Lights up in red when connected to power. Lights up in green during operation. B. Fresh-air / lonizer indicator Lights up when the fresh-air •• •• or lonizer operation. C. LCD operation display D.
Page 495
REMOTE CONTROL FAN SPEED and AUTO FAN button START/STOP button I FEEL temperature sensing mode button Operation mode selection button COOLING HEATING AUTO COOL/HEAT ROOM temperature display button SLEEP button HORIZONTAL Airflow direction AUTO-CONTROL button FRESH HORIZONTAL Airflow direction AUTO-CONTROL button CLOCK button IONIZER button TIMER SET button...
Page 496
OPERATION PROCEDURE TURNING ON THE AIR CONDITIONER Press START/STOP button (2) to turn on the air condi t ioner on. Indicator (A) on the air conditioner will light up, indicating that the unit is in operation. Note that the LCD operation display (17) will always show the last mode of operation and previous function used.
Page 497
AUTO COOLING/HEATING OPERATION Select the AUTO mode by pressing MODE button (4). Switch to the desired FAN SPEED or to AUTO FAN by pressing button (1). Select suitable temperature setting. The air flap will automatically move to either horizontal air delivery for cooling or to vertical air delivery for heating. At start, the air FRESH conditioner will select its mode of operation according to the room temperature and the temperature setting.
Page 498
TIMER OPERATION Press TIMER select button (12) to activate the timed operation mode. Each time you press TIMER button (12), one of the following four operation modes will appear on the LCD disp lay. The operation modes are sequenced in turn in the direction of arrow. During Timer operation, the indicator on the air conditioner will light up.
Page 499
AIR DIRECTION OPERATION 1.Air Direction Positioning Press button (8) to position the air flap to any desired angle. 2.Automatic Vertical Air Swing FRESH Press button (7) to activate the auto air swing. Press button (7) to deactivate this function. TURNING OFF THE AIR CONDITIONER Press START/STOP button (2) to turn off the air conditioner.
Page 500
FRESH AIR FUNCTION (optional) Press the FRESH AIR button (13) to activate the Fresh air function press FRESH the button, the fresh air function will run as continues-cycle by cycle-off. IONIZER AND ELECTROSTATIC FILTER Press the IONIZER button (10) to activate the lonizer and Electrostatic Filter function , if the lonizer switch at ON position, the blue indicator on FRESH the lonizer lights up.
Page 501
PROTECTION MODES Your air-conditioner includes several auto protection modes which enables you to use it virtually at any time and in any season regardless of the outdoor temperature. Some of the protection modes are listed below: Mode Operation Protection Controlled remedy conditions from...
Page 502
CARE AND MAINTENANCE Before performing any maintenance procedure, make sure to disconnect the air conditioner from the power. CLEANING THE AIR FILTER Your air conditioner is provided with a filter cleaning indicator. When the indicator (E)lights up, the filters should be removed for cleaning ••...
Page 503
OPERATING TIPS Set a suitable room temperature; excessively low room temperature is not good for your health and wastes electricity. Avoid frequent setting of the temperature. During cooling, avoid direct sun. Keep curtains and blinds closed. Close doors and windows to keep the cool air in the room. Avoid generating heat or using of heating appliances while the air conditioner in cooling mode.
Page 504
PRECAUTIONS Use the proper electrical fuse.. Do not pull out the power cord unless the unit is turned off. Do not turn on or off air conditioner by inserting the power cord. Do not obstruct or block the air inlet or air outlet of the air conditioner.
Page 505
BEFORE CALLING FOR SERVICE Before calling for service, please check the following common malfunctions and correct it as needed. Problem Cause Remedy Plug in the power Unit does not Unit not connected cord. operate. Stand- to power by indicator does Check main fuse.
Page 506
•• •• INSTALLATION INSTRUCTIONS ENGLISH INSTRUCTIONS D'INSTALLATION FRANCAIS INSTALLATIONSANLEITUNG DEUTSCH INSTRUCCIONES DE INSTALACION ESPANOL ISTRUZIONI PER L'INSTALLAZIONE ITALIANO CONTENT...
Page 507
INSTALLATION INSTRUCTIONS E N G L I S H 1. ACCESSORIES SUPPLIED WITH AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNITS 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4. ELECTRICAL REQUIREMENTS 5. INSTALLATION OF THE INDOOR UNIT 6. CONDENSATE HOSE CONNECTION 7.
Page 508
I N S T A L L A T I O N I N S T R U C T I O N S FOR SPLIT WALL MOUNTED AIR CONDITIONER LOCATION OF INDOOR AND ACCESSORIES SUPPLIED WITH OUTDOOR UNITS THE AIR CONDITIONER Select the location considering the following: Shape Name...
Page 509
Fig.3 Length of electric cable to mains 950mm 1800mm •• • • Fig 3 80 mm Fig.4 Direction of tubing 50 mm 50 mm •• •• 2300 mm Fig 4 Fig.5 1. To attach 2. To remove 100 mm 100 mm 400 mm 500 mm 100 mm...
Page 510
INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) CAUTION New Refrigerant Air Conditioner Installation THIS AIR CONDTIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER. R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx.
Page 511
ELECTRICAL REFRIGERATION TUBE ROUTING REQUIREMENTS 1. There are five possible routes for installing the refrigeration tube as shown. Electrical wiring and connections should be made by qualified 2. For route (6), cut the bottom notch in the rear. electricians and in accordance with local electrical codes and 3.
Page 512
PENETRATION OF WALL FOR TUBING CONDENSATE HOSE 1. Mark the location of the hole on either side of the mounting CONNECTION plate as shown. and drill it at a 5 downward angle, as shown. 1. Attach the condensate drain hose to the corrugated hose in the 2.
Page 513
ELECTRICAL CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS 1. To connect the indoor unit to the outdoor unit MULTIPLE WIRE POWER CABLE use the following electrical cables, protected for outdoor use: Cooling and heating model: Multiple wire cable (220-240V, 50Hz). 5 wires x 1.5 mm (WNG18) 5 wires x 2.5 mm (WNG24) 2 wires x 0.5 mm - for low voltage Fig18...
Page 514
MODE RESET COOL HEAT 3N L Power Cord L N 4 5 6 Fig.20b for 1PH Power Supply to Outdoor Unit 1.Indoor unit terminal 2.Ground wire 3.Indoor twin wire cable 4.Indoor coil 5.Resistor 6.Twin wire cable 7.Multiple wire cable 8.Cable clamp 9.Outdoor twin wire terminal Fig20b A.OUTDOOR B.INDOOR...
Page 515
REFRIGERANT TUBING Tightening TUBE SIZE TORQUE torques of unions Liquid line 1/4" 15-20 N.M. and valve caps: Suction line 3/8" 30-35 N.M. CONNECT THE INDOOR TO THE OUTDOOR UNIT Suction line 1/2" 50-54 N.M. Suction line 5/8" 75-78 N.M. The indoor unit contains a small quantity of refrigerant. Do not unscrew the nuts from the unit until you are ready to connect the Fig.22 Fig.23...
Page 516
INSTALL THE AIR-FRESH HOSE (optional) A 5m of air-refreshing hose is supplied •• •• with this equipment. You can lengthen the hose with another hose supplied by the pro fessional installer in the installation if it is needed. Use the hose elbow and clamps to joint the smaller end ( 30) of the added hose with the original one, and then fix the other end with the interface of the propeller...
Page 517
FINAL TASKS 1. Replace all valve caps and ensure that they are tightened properly. 2. Fill gaps on the wall between hole sides and tubing with sealer. 3. Attach wiring and tubing to the wall with clamps where necessary. 4. Operate the air conditioner together with the customer and explain all functions. 5.